Ardmac Ready to go Modular Data Centres w/HAC

SECURITY SYSTEMS • Access Control - Tridium Access control integration , Niagra 4 with Biometric access control on main doors​ • CCTV - HD Video Appliance 8 Port 8 TB. 8 x 2.0 MP, WDR, LightCatcher, Day/Night, Indoor Dome, 3-9mm f/1.4​ • Intruder Alarm - HKC intruder panel with BMS integration PIR and door sensors​ • System can be standalone or tie into site wide systems​ ELECTRICAL SYSTEMS • Lighting – LED lighting; 500lux ​ • Type 1, 2, 3 surge protection​ IT INFRASTRUCTURE • IT Racks - 600mm x 1200mm racks​ • Plenum – hot and cold aisle containment with door access to hot aisle​ TESTING Air leakage testing included at FAT as part of fire suppression system install​ COMPLIANCE CE Certification, EN 1090, ISO 9001, EN/UL/ UKAS and Local codes

SUMMARY OF TECHNICAL SPECIFICATIONS POWER MODULES MV POWER CONNECTION Transformer & RMU in a Packaged Substation LV POWER 2 No. Trains (N+N) LV SWITCHGEAR • Critical, Non-Critical, Mechanical & Generator change over boards • UPS – Modular UPS & Batteries with 5 mins autonomy @ EOL • Distribution to IT Space – Cable or Busbar Energy Efficient Cooling (100kW) – N+1 Power Monitoring & Quality

Energy metering Branch metering BMS Integration