UVL - LOW SIDEWALL CANOPY With Capture Jet ™ UV and Capture Jet ™ for High Effciency Extraction and Odour treatment
Overview:
Halton UVL Low Sidewall hoods are designed for effcient capture and extraction of the emissions from fryers and grills in Quick Service Restaurants where treatment of vapours & odours is required before discharging air into sensitive environments. The Capture Jet™ effectively captures the contaminated air with minimum exhaust airflow, the flame arrestor flters effciently separate particles from the thermal plume and the Capture Ray™ UV-C neutralizes grease vapours and associated odour.
Features:
Typical Section & Plan:
• Effective: Capture Jet™ reduces energy usage with up to 50% lower exhaust airflow than normal wall hoods. (Performance tested to ASTM F1704). • Efficient: KSA Filters for up to 95% removal of particles 10µm size and above. Capture Ray™ UVC lamps neutralize grease and associated odour. • Safe: KSA Filters for UL1046 certifed flame arrestance. • Hygienic: Stainless steel (AISI 304), welded construction. • Ease: T.A.B.™ testing and balancing taps to allow simple airflow rate balancing & commissioning. UV Racks are easily removed for maintenance. • Lights: LED down Lights provide Warm light at 500 Lux. • Options: Cladding above hood can have optional return for plate shelf (see image right) or perforated front face for low velocity supply of make-up air.
Capture Jet Fan
Slide Damper
KSA Filter 500x330x50
Capture Jet
Typical End View
Exhaust Collar
375ID
Capture Jet Fan Speed Controller
Capture Jet™ technology Up to 50%
Cyclonic filter 95% efficient on 10um and above particles
reduction in airflow rates
Capture Jet Fan Collar
Typical Collar / Fan Size
T.A.B.™ technology Quick airflow rates measurement
Capture Ray™ technology Neutralises grease vapours and particles
*For dimensions refer to project drawing
Recommended Combinations:
Integrated supply air Better smoke capture and comfort
Built-in Fire Suppression Engineered & pre-installed from factory
Impregnated Carbon Filter Reduces Urban Pollution
3
3
3
3
ALLIED MEMBER
ALLIED MEMBER
R
R
Typical Specification Text:
Kitchen Exhaust Hood must be low height sidewall type (1) with Capture Jet™, UL1046 Certifed Cyclonic Filters (KSA), Capture Ray™ UV-C lamps, T.A.B.™ pressure ports and LED Down lights. The hood will be designed to performance standard ASTM1704 and manufactured from 1.2 mm AISI 304 Satin Finish with fully welded exhaust plenum. The hood will be supplied with ANSUL fre suppression and Plate Shelf option or perforated Front for integrated make-up air.