MC Glide Fire Alarm/Control Cable TM - Dual Rated Type MC/FPLP Plenum Rated Technical Specifications Armored Fire Alarm/Control Cable

AFC Cable Systems Kaf-Tech Click brand for more product info

Grounding ꞏ One or More Grounding Conductors May Be Bare or Insulated Green, See Chart Below Neutral Conductor ꞏ White (Where Applicable) Maximum Voltage Rating ꞏ 300V (FPLP) ꞏ 600V (MC) References & Ratings ꞏ UL 66, 83, 1424, 1479, 1569, 1581, 2556, File Reference E80042 & E83514 ꞏ NEC ® 300.22(C), 330, 392, 430.2, 501, 502, 503, 504, 505, 518, 530, 645, 725, 760.154(A) ꞏ NEC ® 300.22 (C) Other Spaces Used For Environmental Air (Plenums) ꞏ NFPA 262 (formerly UL 910) Plenum Rated - Type FPLP ꞏ UL classified 1, 2, and 3, hour through (Fire) penetration product R14141 ꞏ Cable tray rated, install per NEC ® ꞏ Federal Specification A-A-59544 (formerly J-C-30B) ꞏ Meets all applicable OSHA and HUD requirements ꞏ May be surface mounted, fished and /or embedded in plaster ꞏ Made in USA of US and /or imported materials ꞏ US Patent 11,101,056 & D935,731

Interlocked Galvanized Steel Strip (Color-Coded Red)

Assembly Tape

Copper Conductors

Copper Ground

Nylon Thermoplastic TFN or THHN Insulation

Armor ꞏ Interlocked Galvanized Steel Strip (Red) Conductors ꞏ Solid Copper Conductor Insulation ꞏ TFN 16 AWG and/or THHN 14 & 12 AWG Assembly ꞏ Polyester Assembly Tape; Twisted Shielded: Laminated Aluminum/Mylar ® Shield with Tinned Copper Drain Wire Maximum Temperature Rating ꞏ FPLP: 105°C (Dry) ꞏ MC: 90°C (Dry)