Type MCI-A Cables - Armor + Bond = Equipment Grounding Path Click brand for more product info
MC-Stat ® & MC-Stat ® Lite Cable Type MCI-A Cables (120/208V Colors & 277/480V Colors) Technical Specifications Healthcare Facility Cables
AFC Cable Systems Kaf-Tech
References & Ratings ꞏ UL 83,1479,1569,1581, 2556, File Reference E80042 ꞏ NEC ® 230, 250, 300, 330, 392, 396, 501, 502, 503, 505, 517, 518, 520, 530, 645 ꞏ NEC ® 300.22 (C) Other Spaces Used For Environmental Air (Plenums) ꞏ UL classified 1, 2, and 3, hour through (Fire) penetration product R14141 ꞏ Cable tray rated, install per NEC ® ꞏ Federal Specification A-A-59544 (formerly J-C-30B) ꞏ Meets all applicable OSHA and HUD requirements ꞏ May be surface mounted, fished and /or embedded in plaster ꞏ Made in USA of US and /or imported materials ꞏ Aluminum armored cables are RoHS compliant
Full Size Aluminum Bonding/ Grounding Conductor
Green Ground
Interlocked Steel or Aluminum Armor ColorSpec® ID System
Wrap Free
Copper Conductors
THHN Copper Conductor & Protective Polypropylene Cover
Armor ꞏ Interlocked Galvanized Steel Strip or Interlocked Aluminum Strip (Light Green Striped) Conductors ꞏ Solid or Stranded Copper Conductor Insulation ꞏ Type THHN with Protective Polypropylene Covering on Each Insulated Conductor (No Assembly Tape) Maximum Temperature Rating ꞏ 90°C (Dry) Grounding ꞏ Two Grounding Means - (1) Combined Armor and Full-Sized Aluminum Ground
Conductor per NEC® 250.118(10)(b), (2) Full-Sized Green Insulated Copper Grounding Conductor per NEC® 250.118(1)
Neutral Conductor ꞏ White 120 /208V ꞏ Gray 277 /480V Maximum Voltage Rating ꞏ 600V