Chino Product Catalog_V02 web

Armored Cables (Type AC)

AFC Cable Systems Kaf-Tech Click brand for more product info

HCF-90 ® Type AC Steel Healthcare Facilities Cable (120/208V Colors & 277/480V Colors) Technical Specifications

Features & Benefits ꞏ Interlocked galvanized steel strip ꞏ Easy to identify green armor ꞏ Full size green insulated copper grounding conductor plus armor/bond wire combination provides redundant ground or isolated grounding capability References & Ratings ꞏ UL 4, 83, 1479, 1581, 2556, File Reference E7330 ꞏ NEC ® 250.118(8), 300.22(C), 320, 392, 517.13, 518, 645 ꞏ NEC ® 300.22(C) Environmental Air Handling Spaces (Plenum) ꞏ UL Classified 1, 2, and 3 hour through (Fire) penetration product, R14141

Interlocked Galvanized Steel Armor (Green)

Insulated Bushing

Bare Aluminum Bonding Strip

Green Insulated Copper Ground

Paper Wrap on Each Conductor

Nylon Thermoplastic THHN Insulation

Armor & Jacket ꞏ Interlocked Galvanized Steel Strip (Green) Conductors ꞏ Solid Copper Conductor Insulation ꞏ THHN Conductor Insulation Covering ꞏ Moisture Resistant Fire Retardant Paper Wrap Maximum Temperature Rating ꞏ 90°C (Dry) Type ACTHH Grounding ꞏ 16 AWG Integral Bond Wire/Armor Combination per 250.118(8) and Green Insulated Copper Grounding Conductor per 250.118(1)

ꞏ Cable Tray Rated, install per NEC ® ꞏ Federal Specification A-A-59544 (formerly J-C-30B) ꞏ Meets all applicable OSHA and HUD Requirements ꞏ Made in USA of US and/or imported materials

Neutral Conductor ꞏ White 120/ 208V ꞏ Gray 277/ 480V Maximum Voltage Rating ꞏ 600V

For bond wire termination details, click on these links for MC & AC Cables Installation and Installation Instructions.

8

Made with FlippingBook - Online magazine maker