1. Maximum Winding Temperature Above Ambient at Rated Load This rating is the highest temperature rise of transformer windings above the surrounding ambient temperature when operating at rated load. •

Rated Load is the maximum continuous load (in kVA) that the transformer is designed to handle under standard conditions without exceeding temperature limits.

Typical Limits o

Average winding rise: 65°C above ambient Hot-spot rise: 85°C above ambient Ambient temperature design is typically 30°C

o

Standard Conditions o

Within designed cooling method parameters

o

Total Hot-Spot Temperature permissible is Ambient (30°C) + Hot-spot rise (85°C) = 115°C maximum Standard Reference is IEEE C57.12.00 and C57.12.90 for liquid-filled transformers. Higher temperatures accelerate insulation aging Maintaining limits ensures expected service life and reliability under normal operating conditions.