I. OPEN DELTA – OPEN DELTA: 4-Wire, 3-Phase Service

A B C N

H1 H2

H1 H2

X3

X1

X3

X1

Tank GND

Tank GND

X2

X2

a b c n

Primary Wiring: With a Delta connected high- voltage side, the H1 terminal of each transformer is connected to the H2 terminal of the adjacent transformer in circular fashion. These H1/H2 pairs are then connected to the primary phases. Secondary Wiring: This secondary connection supports both single-phase and three-phase loads. 240∆/120 banks are popular due to their ability to serve multiple customer types from the same transformer bank: single-phase for customers with lighting and small motor loads,