Compressors & Parallel Racks
RECIP. LARGE PARALLEL RACKS | Customer Value › Applicable for multiple refrigerants and scenarios , with a cooling capacity of 210 HP › Numerous non-standard customization for various sites › High energy efficiency, reducing operating costs , LT two- stage reciprocat- ing parallel racks save at least 30% energy while the MT racks save around 5% › The racks supports VFD drives for more efficient energy regulation › Reliable operation, safe and stable › System with good oil return and long service life › Compact structure, small footprint | Benefits at a Glance › Multi-compressor parallel design, optional cooling capacity range: 13 HP - 210 HP › Refrigerant options: R448, R449/R404A and others › Multiple non-standard options are available. › Self-developed special refrigeration compressors, reliable and efficient › Compressors and system with separate pressure switches and electric protection for reliable operation
| Application Range
Recip. Compressor
Mode
MT
LT, Single-stage
LT, Two-stage
Refrigerant Evaporating Temp.
R448/R449
R404A
R448/R449
R404A
R448/R449
R404A
-18~ +7
-18~ +4
-37~ -18
-40~ -18
-50~ -24
-50~ -24
| Recip. Large Parallel Racks LT Two-stage Parallel Racks
Evaporating Temp.: -50 ℃ Evaporating Temp.: -45 ℃ Evaporating Temp.: -40 ℃ Evaporating Temp.: -35 ℃ Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW)
Compressor Models & QTY
Rack Models
— —
— —
— —
— —
VPM2257OR-30 VPM2257OR-40 VPM3257OR-45 VPM3257OR-60 VPM3257OR-90 VPM4257OR-120 VPM5257OR-150 VPM6257OR-180
2*06CC550 2*06CC675 3*06CC550 3*06CC675 3*06CC899 4*06CC899 5*06CC899 6*06CC899
17.4
11.48 19.38 17.22 29.07
23.94 41.06 35.91 61.59 82.62 110.16 137.7 165.24
13.4 22.2 20.1 33.3
19.96
13.78
25.06
16.5
32.16
26.1
29.94 42.99 57.32 71.65 85.98
20.67 30.66 40.88
37.59 52.23 69.64 87.05 104.46
24.75 36.12 48.16 60.2 72.24
48.24 65.64 87.52 109.4 131.28
41.7
47.25
55.6 69.5 83.4
63
51.11
78.75
61.32
94.5
› Three-stage oil separator with an efficiency of >98% › Integrated structure design, compact and easy to install
LT Parallel Racks
Evaporating Temp.: -40 ℃ Evaporating Temp.: -35 ℃ Evaporating Temp.: -30 ℃ Evaporating Temp.: -25 ℃ Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW)
| Standard Configuration
Compressor Models & QTY
Rack Models
LT Two-stage
MT/LT Single-stage
LT Single-stage & MT
› Compressor › Subcooler › Mechanical Oil Equalizer › Integrated vertical reservoir › Muffler › Removable liquid supply filter drier › Gas-liquid separator › Exhaust/return/liquid supply stop valve or ball valve
› Compressor › Mechanical Oil Equalizer › Integrated vertical reservoir › Exhaust check valve › Muffler › Alarm relay › Reservoir outlet filter drier › Exhaust/return/liquid supply stop valve or ball valve
› Compressor › Mechanical Oil Equalizer › Integrated vertical reservoir › Return air filter › Gas-liquid separator (standard for LT ver- sion, no for MT version) › Reservoir outlet filter drier › Muffler › Exhaust/return/liquid supply stop valve or ball valve
VPM2203OR-30 VPM2203OR-50 VPM3203OR-45 VPM3203OR-60 VPM3203OR-90 VPM4203OR-120
2*06ER450 2*06ER475 3*06ER450 3*06ER475 3*06ER399 4*06ER399
12.88 18.84 19.32 28.26 41.22 54.96 60.06
12.94 18.64 19.41 27.96 40.35
20.42 29.04 30.63 43.56 58.56 78.08
17.14
28.94 40.96 43.41 61.44 78.78 105.04 119.74
21.26 29.26 31.89 43.89 59.67 79.56 88.93 99.45 108.82 119.34
38.58
25.24
23.84 25.71 35.76 49.71 66.28 73.55 82.85 90.12 99.42
54.9
34.8
57.87 82.35 102.42 136.56 157.32
37.86
52.2
70.08 93.44 104.88
53.8
VPM5203OR-130 3*06ER399+2*06ER475
58.99 67.25 72.44
87.6 97.6
VPM5203OR-150
5*06ER399
68.7 73.8
131.3
170.7
116.8
VPM6203OR-160 4*06ER399+2*06ER475
107.12 117.12
146
191.46
128.24 140.16
VPM6203OR-180
6*06ER399
82.44
80.7
157.56
204.84
| Optional LT Two-stage
MT Parallel Racks
MT/LT Single-stage
T Single-stage & MT
Evaporating Temp.: -15 ℃
Evaporating Temp.: -12 ℃
Evaporating Temp.: -10 ℃
Evaporating Temp.:-5 ℃
Compressor Models & QTY
› Danfoss, Carel controllers › Number of liquid supply and gas return branches › Electronic Oil Equalizer › Multiple suction pressure racks › Inverter › Remote control
› Subcooler › Danfoss, Carel controllers › Electronic Oil Equalizer › Split horizontal/vertical reservoir
› Subcooler › Danfoss, Carel controllers › Electronic Oil Equalizer › Split horizontal/vertical reservoir › Condensing pressure switch › With shock-absorbing hoses › Multiple suction pressure racks › Inverter › Remote control
Cooling Capacity Q (kW)
Cooling Capacity Q (kW)
Cooling Capacity Q (kW)
Cooling Capacity Q (kW)
Rack Models
Input Power P(kW)
Input Power P(kW)
Input Power P(kW)
Input Power P(kW)
VPP2203OR-30 VPP2203OR-40 VPP3203OR-45 VPP3203OR-75 VPP3203OR-105
2*06EM450 2*06EM475 3*06EM450 3*06EM475 3*06EM499
49.02
24.78 37.62 37.17 56.43 87.06 95.66 105.87 116.08 124.68 145.1 153.7 174.12
57.26 89.92 85.89 134.88 199.89 223.18 244.85 266.52 289.81 333.15 356.44 399.78
26.94 40.72 40.41 61.08
63.2
28.34 42.78 42.51 64.17 95.52 106.46 116.91 127.36 138.3 159.2 170.14 191.04
79.72 123.98 119.58 185.97 250.92 291.26
31.66 47.84 47.49 71.76 102.6 116.24 126.52
77.5
98.88
› Condensing switch › Exhaust check valve › Hot gas defrost system
73.53 116.25 180.78
94.8
148.32 213.48
92.4
VPP4203OR-120 2*06EM499+2*06EM475 198.02
102.32 112.76 123.2 133.12
241.2
VPP4203OR-130 3*06EM499+06EM475
219.53 241.04
262.92 284.64 312.36 355.8 383.52 426.96
312.91
VPP4203OR-140
4*06EM499
334.56
136.8
NOTES
3 ) Power supply for the control operation: one-phase 220V/50Hz 4 ) If the racks are aiming to operate at different evaporating temp. or at too high or too low ambient temp., please contact us. 5 ) For an application at a temp. of ※ (i.e., -50 ° C), please contact our technicians.
1 ) The cooling capacity and input power are based on an ambient temp. of 32 ° C, the condensing temp. of 45 ° C, no liquid subcooling; and the temp. of the interstage cooling liquid for two-stage is 4.4 ° C. For example, if SIT+2.8>4.4 ° C, the temp. is SIT+5.6 ° C 2 ) Power supply for the racks: three-phase 380V/50Hz
VPP5203OR-155 3*06EM499+2*06EM475 258.28
374.9 418.2
150.44
VPP5203OR-175
5*06EM499
301.3
154
171
VPP6203OR-190 4*06EM499+2*06EM475 318.54
163.92
458.54 501.84
184.64 205.2
VPP6203OR-210
6*06EM499
361.56
184.8
11 | Industrial Heating & Cooling – Comprehensive Solutions