工业冷热全场景解决方案_2026 (EN)

Compressors & Parallel Racks

RECIP. LARGE PARALLEL RACKS | Customer Value › Applicable for multiple refrigerants and scenarios , with a cooling capacity of 210 HP › Numerous non-standard customization for various sites › High energy efficiency, reducing operating costs , LT two- stage reciprocat- ing parallel racks save at least 30% energy while the MT racks save around 5% › The racks supports VFD drives for more efficient energy regulation › Reliable operation, safe and stable › System with good oil return and long service life › Compact structure, small footprint | Benefits at a Glance › Multi-compressor parallel design, optional cooling capacity range: 13 HP - 210 HP › Refrigerant options: R448, R449/R404A and others › Multiple non-standard options are available. › Self-developed special refrigeration compressors, reliable and efficient › Compressors and system with separate pressure switches and electric protection for reliable operation

| Application Range

Recip. Compressor

Mode

MT

LT, Single-stage

LT, Two-stage

Refrigerant Evaporating Temp.

R448/R449

R404A

R448/R449

R404A

R448/R449

R404A

-18~ +7

-18~ +4

-37~ -18

-40~ -18

-50~ -24

-50~ -24

| Recip. Large Parallel Racks LT Two-stage Parallel Racks

Evaporating Temp.: -50 ℃ Evaporating Temp.: -45 ℃ Evaporating Temp.: -40 ℃ Evaporating Temp.: -35 ℃ Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW)

Compressor Models & QTY

Rack Models

— —

— —

— —

— —

VPM2257OR-30 VPM2257OR-40 VPM3257OR-45 VPM3257OR-60 VPM3257OR-90 VPM4257OR-120 VPM5257OR-150 VPM6257OR-180

2*06CC550 2*06CC675 3*06CC550 3*06CC675 3*06CC899 4*06CC899 5*06CC899 6*06CC899

17.4

11.48 19.38 17.22 29.07

23.94 41.06 35.91 61.59 82.62 110.16 137.7 165.24

13.4 22.2 20.1 33.3

19.96

13.78

25.06

16.5

32.16

26.1

29.94 42.99 57.32 71.65 85.98

20.67 30.66 40.88

37.59 52.23 69.64 87.05 104.46

24.75 36.12 48.16 60.2 72.24

48.24 65.64 87.52 109.4 131.28

41.7

47.25

55.6 69.5 83.4

63

51.11

78.75

61.32

94.5

› Three-stage oil separator with an efficiency of >98% › Integrated structure design, compact and easy to install

LT Parallel Racks

Evaporating Temp.: -40 ℃ Evaporating Temp.: -35 ℃ Evaporating Temp.: -30 ℃ Evaporating Temp.: -25 ℃ Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW) Cooling Capacity Q (kW) Input Power P(kW)

| Standard Configuration

Compressor Models & QTY

Rack Models

LT Two-stage

MT/LT Single-stage

LT Single-stage & MT

› Compressor › Subcooler › Mechanical Oil Equalizer › Integrated vertical reservoir › Muffler › Removable liquid supply filter drier › Gas-liquid separator › Exhaust/return/liquid supply stop valve or ball valve

› Compressor › Mechanical Oil Equalizer › Integrated vertical reservoir › Exhaust check valve › Muffler › Alarm relay › Reservoir outlet filter drier › Exhaust/return/liquid supply stop valve or ball valve

› Compressor › Mechanical Oil Equalizer › Integrated vertical reservoir › Return air filter › Gas-liquid separator (standard for LT ver- sion, no for MT version) › Reservoir outlet filter drier › Muffler › Exhaust/return/liquid supply stop valve or ball valve

VPM2203OR-30 VPM2203OR-50 VPM3203OR-45 VPM3203OR-60 VPM3203OR-90 VPM4203OR-120

2*06ER450 2*06ER475 3*06ER450 3*06ER475 3*06ER399 4*06ER399

12.88 18.84 19.32 28.26 41.22 54.96 60.06

12.94 18.64 19.41 27.96 40.35

20.42 29.04 30.63 43.56 58.56 78.08

17.14

28.94 40.96 43.41 61.44 78.78 105.04 119.74

21.26 29.26 31.89 43.89 59.67 79.56 88.93 99.45 108.82 119.34

38.58

25.24

23.84 25.71 35.76 49.71 66.28 73.55 82.85 90.12 99.42

54.9

34.8

57.87 82.35 102.42 136.56 157.32

37.86

52.2

70.08 93.44 104.88

53.8

VPM5203OR-130 3*06ER399+2*06ER475

58.99 67.25 72.44

87.6 97.6

VPM5203OR-150

5*06ER399

68.7 73.8

131.3

170.7

116.8

VPM6203OR-160 4*06ER399+2*06ER475

107.12 117.12

146

191.46

128.24 140.16

VPM6203OR-180

6*06ER399

82.44

80.7

157.56

204.84

| Optional LT Two-stage

MT Parallel Racks

MT/LT Single-stage

T Single-stage & MT

Evaporating Temp.: -15 ℃

Evaporating Temp.: -12 ℃

Evaporating Temp.: -10 ℃

Evaporating Temp.:-5 ℃

Compressor Models & QTY

› Danfoss, Carel controllers › Number of liquid supply and gas return branches › Electronic Oil Equalizer › Multiple suction pressure racks › Inverter › Remote control

› Subcooler › Danfoss, Carel controllers › Electronic Oil Equalizer › Split horizontal/vertical reservoir

› Subcooler › Danfoss, Carel controllers › Electronic Oil Equalizer › Split horizontal/vertical reservoir › Condensing pressure switch › With shock-absorbing hoses › Multiple suction pressure racks › Inverter › Remote control

Cooling Capacity Q (kW)

Cooling Capacity Q (kW)

Cooling Capacity Q (kW)

Cooling Capacity Q (kW)

Rack Models

Input Power P(kW)

Input Power P(kW)

Input Power P(kW)

Input Power P(kW)

VPP2203OR-30 VPP2203OR-40 VPP3203OR-45 VPP3203OR-75 VPP3203OR-105

2*06EM450 2*06EM475 3*06EM450 3*06EM475 3*06EM499

49.02

24.78 37.62 37.17 56.43 87.06 95.66 105.87 116.08 124.68 145.1 153.7 174.12

57.26 89.92 85.89 134.88 199.89 223.18 244.85 266.52 289.81 333.15 356.44 399.78

26.94 40.72 40.41 61.08

63.2

28.34 42.78 42.51 64.17 95.52 106.46 116.91 127.36 138.3 159.2 170.14 191.04

79.72 123.98 119.58 185.97 250.92 291.26

31.66 47.84 47.49 71.76 102.6 116.24 126.52

77.5

98.88

› Condensing switch › Exhaust check valve › Hot gas defrost system

73.53 116.25 180.78

94.8

148.32 213.48

92.4

VPP4203OR-120 2*06EM499+2*06EM475 198.02

102.32 112.76 123.2 133.12

241.2

VPP4203OR-130 3*06EM499+06EM475

219.53 241.04

262.92 284.64 312.36 355.8 383.52 426.96

312.91

VPP4203OR-140

4*06EM499

334.56

136.8

NOTES

3 ) Power supply for the control operation: one-phase 220V/50Hz 4 ) If the racks are aiming to operate at different evaporating temp. or at too high or too low ambient temp., please contact us. 5 ) For an application at a temp. of ※ (i.e., -50 ° C), please contact our technicians.

1 ) The cooling capacity and input power are based on an ambient temp. of 32 ° C, the condensing temp. of 45 ° C, no liquid subcooling; and the temp. of the interstage cooling liquid for two-stage is 4.4 ° C. For example, if SIT+2.8>4.4 ° C, the temp. is SIT+5.6 ° C 2 ) Power supply for the racks: three-phase 380V/50Hz

VPP5203OR-155 3*06EM499+2*06EM475 258.28

374.9 418.2

150.44

VPP5203OR-175

5*06EM499

301.3

154

171

VPP6203OR-190 4*06EM499+2*06EM475 318.54

163.92

458.54 501.84

184.64 205.2

VPP6203OR-210

6*06EM499

361.56

184.8