Fluke CV Series ClirVu ® Infrared Windows
Quick & Easy Installation in 5 minutes or less
Compliance without compromise. Safety without sacrifice. Increase the safety and speed of electrical thermal imaging inspections with the Fluke ClirVu ® IRWindows Reduce the risk of arc-flash and electrocution, increase the safety of your personnel and reduce the time and cost of preventive maintenance. • Save time with a quick and easy 5 minutes or less installation - One technician - One hole with standard Greenlee ® punch - Panel door does not need to be removed - Grounds instantly to metal enclosure with patent-pending AutoGround™ process - Maintains panel arc test ratings up to 63kA when properly installed • Torture Tested™ to the highest arc blast test ratings - IEEE C37.20.7: 63 kA Arc tested at KEMA, UL50/50E/50V, UL1558, IEC60529-1: IP67, IEC 60068, NEMA 4/12, CSA C22.2 NO. 14-13:2012, and CE • Convenience of both quick turn (CV400, CV300, CV200) or security keyed access (C401, CV301, CV201) • Fluke IRWindows offered in three sizes 50 mm, 75 mm and 95 mm • Work permit requirements and NFPA 70E processes are significantly reduced • Full PPE is often not required so inspections are done faster and more comfortable • Lifetime replacement warranty against manufacturing defects
Fluke CV400
Fluke CV300
Fluke CV200
Specifications
CV400 CV401 CV300 CV301 CV200 CV201
Size
95 mm
75 mm
50 mm
Voltage Range
Any
Included Accessories Hand Turn Door Latch (CV200, 300 & 400), Security Key Door Latch (CV201, 301 & 401) and Warranty Statement. Fluke IR Windows are supplied complete, assembled and ready for installation.
NEMA Environment Type
Type 4/12 (indoor/outdoor)
AutoGround™ ClirVu ® Optic
Yes Yes
Operating temperature
-40 ºC to + 232 ºC and + 260ºC Intermittent EZAC & ZA-27 High Strength Zinc/ Aluminum Alloy
Body material
Ratings and testing Arc-Tested (IEEE C37.20.7)
63 kA for 30 cycles @ 60Hz at KEMA
Ordering Information
UL 50V component recognition
Yes
FLUKE-CV200
95 mm, Infrared Window, Hand Turn Door Latch 75 mm, Infrared Window, Security Key Door Latch 75 mm, Infrared Window, Hand Turn Door Latch 50 mm, Infrared Window, Security Key Door Latch 50 mm, Infrared Window, Hand Turn Door Latch
UL 50/NEMA Environmental Rating
NEMA Type 4/12
UL 1558
Yes Yes
FLUKE-CV201
CSA C22.2 No. CSA Type Rating
Type 4
IP rating
IP67 at TUV
FLUKE-CV300
Lloyds Register Vibration rating Humidity rating
Up to 11 kV marine switchgear, indoor or outdoor (offshore only)
IEC60068-2-6 at TUV IEC60068-2-3 at TUV
FLUKE-CV301
Install Actual mounting hole diameter required
115.42 mm
89.89 mm
61.37 mm
FLUKE-CV400
Greenlee Punch Kit = Punch/ Die
742BB = 2984AV/2983AV
739BB = 1431AV/1432AV
76BB = 441AV/442AV
Security
Security Key
Door Latch
Hand Turn Security Key Hand Turn
Key Hand Turn
FLUKE-CV401 95 mm, Infrared Window, Security Key Door Latch
Optics Optic insert diameter
95 mm
75 mm
50 mm
C ontact your local distributor for price and availability. www.fluke.com/au/wtb
www.fluke.com/au/infrared_cameras
Infrared Cameras
61