Test

Fluke VR1710 Single Phase Voltage Quality Recorder

PowerLog Software

Easy-to-use solution for detecting and recording voltage quality problems

The Fluke VR1710 is a single-phase, plug-in voltage quality recorder that provides fast and easy recording of voltage trends, dropouts, harmonics and general power quality including dips and surges to help maintenance and facilities management personnel easily pinpoint the root cause of voltage problems. Voltage quality parameters including RMS average, transients, flicker, and harmonics up to the 32nd are recorded using a user-selected average period from 1 second to 20 minutes. • Fast and easy recording of voltage trends, dropouts and power quality: Easily pinpoint the root cause of single phase voltage problems • Extremely easy to use: Plugs directly into the mains power socket and capture data • Quickly see what happened and when: Min, Max, and Average RMS values (1/4 cycle) with time stamp, transient display (>100 μs) with time stamp • Easily identify problems: Power quality or equipment related Flicker recording to EN 61000-4-15, individual harmonic and THD values with trends • Includes PowerLog software: For quick download, analysis and automatic reporting • Save time: Generate power quality reports automatically with pre-set templates • One year warranty

PowerLog Setup – Simple set up of internal clock, logging periods, and intervals with default values for quick results. PowerLog View – Data presentation showing RMS voltage and harmonic trends, actual transients, summary information and statistics in accordance with EN50160.

Fluke VR1710

Applications Voltage recording

Monitors and records supply voltage; measures RMS average, minimum and maximum values, and checks whether the socket outlet is providing voltage within tolerance. Measure frequency and harmonics; check whether the distorting loads (UPS systems, drives, etc.) are affecting your other equipment.

Distortion measurement

Actual transient display (> 100 µs) with time stamp – Quickly identify issues with included graphical software.

Flicker measurement Voltage transients

Quantify the affects of switching loads on lighting systems.

Capture those intermittent, momentary events that may be affecting your equipment; the full waveform is captured with date, timestamp, and duration.

Specifications Operating voltage

70 V to 300 V Min/Max/Avg RMS value Resolution 0.125 V Number of events 175,000 Dips/Interruptions Yes Time resolution 5 ms Voltage resolution) 0.125 V Over-voltages Yes Frequency Yes Harmonics measurement EN 61000-4-7 (up to 32nd) Flicker measurement EN 61000-4-15 Number of recording channels

Includes PowerLog software

1 Phase to Neutral, 2 Phase/Neutral to Ground

Recording time

1 day to 339 days depending on average time from 1 second to 20 minutes

Transients

Yes

Frequency range

50 Hz ± 1 Hz and 60 Hz ± 1 Hz

Safety category rating CAT II 300 V

Included Accessories USB Cable, PowerLog Software CD, Power Cord Adapter. Ordering Information FLK-VR1710 Voltage Quality Recorder

C ontact your local distributor for price and availability. www.fluke.com/au/wtb

86

Power Quality Analysers

Made with FlippingBook Learn more on our blog