Fluke 1732 and 1734 Three-Phase Electrical Energy Loggers

Energy logging is now within your reach— discover where you’re wasting energy, optimise your facility’s energy use and reduce your bill The Fluke 1732 and 1734 Three-Phase Electrical Energy Loggers introduce a new simplicity to discovering sources of electrical energy waste. Discover when and where energy in your facility is being consumed; from the service entrance to individual circuits. Access and share data remotely with your team via the Fluke Connect ® app so you can maintain safer working distances and make critical decisions in real-time, reducing the need for protective equipment, site visits and check-ins.

Recommended Accessories

I17XX-FLEX 1500 1500A 12 inch iFlex ® Current Clamps (Purchase as individual, 3pk or 4pk) See page 159

I17XX-FLEX 3000 3000A 24 inch iFlex ® Current Clamps (Purchase as individual, 3pk or 4pk) See page 159

Fluke 1734

6000A 36 inch iFlex ® Current Clamps (Purchase as individual, 3pk or 4pk) See page 159 I17XX-FLEX 6000

I40S-EL/3PK 40A Clamp-on Current Transformer 3 pack (Purchase as individual or 3pk) See page 159

Profiling energy usage across your facility helps you identify opportunities for energy savings, and provides you with the data you need to act on them. The new Energy Analyse software package allows you to compare multiple data points over time to build a complete picture of energy usage, which is the first step to reduce the cost of your energy bill. • Key measurements: Automatically capture and log voltage, current, power, power factor, energy and associated values • Fluke Connect ® compatible: View data locally on the instrument, via Fluke Connect mobile app and desktop software or through your facilities’ WiFi infrastructure • Convenient instrument powering: Power instrument directly from the measured circuit • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream • Measure all three phases: With included 3 flexible current probes • Fully integrated logging: Connect other Fluke Connect devices to the Fluke 1734 to simultaneously log up to two other measurement parameters, virtually any parameter available on a Fluke Connect wireless digital multimeter or module • Energy Analyse Plus application software: Download and analyse every detail of energy consumption with our automated reporting • One year warranty

FLUKE-17XX-TL 0.1M Test Lead Set, 1000V CAT III, Non-stackable Connectors; 0.1M; Red/Blk See page 159

FLUKE-17XX-TL 1.5M Test Lead Set, 1000V CAT III, Non-stackable Connectors; 1.5M; Red/Blk See page 159

MP1-MAGNET PROBE1 Magnet Probes for 4mm banana, Set of 4 See page 159

Hanging Strap Kit See page 159 173X-HANGER KIT

Specifications Accuracy Parameter

Range

Max resolution Intrinsic accuracy at reference conditions (% of reading + % of full scale)

1732/UPGRADE Upgrade Kit for 1732 to 1734 See page 160

C17XX Soft case See page 160

Voltage

1000 V

0.1 V 0.1 A 1 A 1 A 10 A 1 A 10 A

± (0.2 % + 0.01 %) ± (1 % + 0.02 %) ± (1 % + 0.02 %) ± (1 % + 0.03 %) ± (1 % + 0.03 %) ± (1.5 % + 0.03 %) ± (1.5 % + 0.03 %) ± (0.7 % + 0.02 %) ± (0.7 % + 0.02 %)

i17xx-flex 1500 12” 150 A 1500 A i17xx-flex 3000 24” 300 A 3000 A i17xx-flex 6000 36” 600 A 6000 A

Included Accessories Power Supply, Voltage Test Leads, 4 x Alligator Clips, 3 x 12 in 1,500A Flexible Current Probe, Soft Case, Energy Analyse Plus Software, Line Cords, Colour Coding Set and Documentation on USB Flash Drive, Magnetic Hanging Strap (1734) and Magnetic Voltage Probes (1734).

Current

i40s-EL clamp

4 A 40 A

1 mA 10 mA 0.01 Hz

Frequency

42.5 Hz to 69 Hz

± (0.1 %)

Aux input

± 10 V DC 0.1 mV

± (0.2 % + 0.02 %) ± (1 % + 0.1 %) ± (5 % + 0.2 %)

Voltage min/max Current min/max THD on voltage THD on current

1000 V

0.1 V

Ordering Information

defined by accessory

defined by accessory

Energy Logger, Basic Version (excl. current probes) Energy Logger, International Version (incl. current probes) Energy Logger, Basic Version with Fluke Connect (excl. current probes) Energy Logger, International Version with Fluke Connect (incl. current probes)

FLUKE 1732/B

1000 % 0.1 % 1000 % 0.1 %

± 0.5 ± 0.5

FLUKE 1732/ INTL

Voltage harmonics 2nd ... 50th Current harmonics 2nd ... 50th

1000 V

0.1 V

≥ 10 V: ± 5 % of reading < 10 V: ± 0.5V

defined by accessory

defined by accessory

≥ 3 % of current range: ± 5 % of reading < 3 % of current range: ± 0.15 % of range

FLUKE 1734/B

Unbalance

100 % 0.1 %

± 0.2

For more information, go to www.fluke.com/au/PQ

FLUKE 1734/ INTL

www.fluke.com/au/PQ