FC1700/FC1900/SF3100/SF4200: EPA 2016 Certification Report

HY-C Company, LLC

Date: November 10, 2016

Project No. G102523311

Page 6 of 16

II.B INFORMATION LOG II.B(1) TEST STANDARD

From May 9, 2016 through June 23, 2016, the unit was tested for EPA emissions. For Wood Forced-Air Furnaces, the test was conducted in accordance with CSA B415.1- 2010. The fuel used for the test run was Oak cordwood. The applicable EPA regulatory limits are: Step 1 – 2016 – 0.93 lbs/MMBtu Output (0.4 g/MJ) – For furnaces rated less than 65,000 Btu/hr Step 1 – 2017 – 0.93 0.93 lbs/MMBtu Output (0.4 g/MJ) – For furnaces rated more than 65,000 Btu/hr Step 2 – 2020 – 0.15 lbs/MMBtu Output (0.026 g/MJ) II.B(2) DEVIATION FROM STANDARD METHOD No deviations from the standards were performed, however, only the applicable sections from each standard were used during all testing. II.C SUMMARY OF TEST RESULTS

The appliance tests resulted in the following performance:

Particulate Emissions: 0.261 lbs/MMBtu Output (0.225 g/MJ) Carbon Monoxide Emissions: 139.44 g/hr Heating Efficiency: 64.1% (Higher Heating Value Basis)

II.D DESCRIPTION OF TEST RUNS

RUN #1 (May 9, 2016). The furnace was set to a category 3 draw rate. The combustion blower was turned on to maintain the desired heat rate. The Test Load weighed 37.51 lbs. and utilized a 7.5 lb. coal bed. The average Btu/hr output was 51,504. Burn time was 3.57 hours. The kg/hr burn rate was 3.89.