GSK Product Pack Jun2023
Recommended products for
Ardmac are pleased to present this catalogue of cleanroom products gleaned from over 45 years delivering controlled environments to customers in the Life Sciences and Advanced Manufacturing sectors. The small selection we have included are the most commonly used products we have designed and installed for Pharmaceuticals clients across the UK, Ireland and Europe. The performance of a room is dependent on products selected and the combination, and collaboration of those products. It makes a huge difference to our clients that we can both advise and go to the market for the Optimal Product arrangement for their space. Ardmac are one of the largest providers of Cleanrooms in Europe and have success- fully delivered many projects throughout the continent and beyond for most of the top 20 Global Pharmaceutical manufacturers, the world’s largest Semi-conductor manufacturer plus many Medical Device companies and Healthcare providers. We work more efficiently by combining Lean construction techniques and the latest BIM technology with our collaboration & field management software in a manner that positively impacts job safety, schedule, quality and cost. Our approach adds value to any Cleanroom Construction project and that is why Ardmac has become a trusted partner for collaborative processes such as IPD (Integrated Project Delivery), customer framework agreements and early engagement. We hope this catalogue provides some guidance for any upcoming projects and myself and the team are available to discuss how we can support GSK with their ongoing project requirements .
Mark Seymour Regional Manager UK
Contents
01. Monobloc Systems 02. Bi-Panel Systems 03. Door Furniture 04. Accessories
Further Info : Ardmac Agile Cleanroom Suites Brochure
2
Building Better Monobloc Systems
3
Partition SM60 Metal coatings and mineral wool core
GSP-0203-E/C
The SM60 partition is designed for Ultra-Clean rooms that must be kept completely free of micro-biological contamination. This partition consists of non combustible modular panels of thickness 60 mm 2.36’’ , made of time-stable materials and no emitting particles. The SM60 partition, providing smooth surfaces easy to clean, is airtight and insulating.
Design
Core
Hydrophobic rock wool plates Density : 80 kg/m 3 (partition) 4.99 lb/ft 3 Fire class according to EN 13501-1: A1
folded edges
Glue : bi-components Polyurethane
profile
metal coating
rock wool core
Facings
Class according to XP P 34-301
Supports
Coatings according to NF EN 10169
Thicknesses (in mm)
coated with polyester 25 μm lacquer coated with PVDF 35 μm lacquer
0,5 0.02’’
0,6* 0.02’’ 0,8 0.03’’
llla lVb
0,6 0,6
Steel sheet S280 GD, hot-dip galvanised Z225 (225g/m² of zinc on the 2 faces) or similar
coated with PVC 120 μm
Vc
coated with a complex of polyester lacquer and PET film of total thickness 55 μm
0,6
Vc
polished S4
0,6
0,8
Smooth stainless steel sheet of slight 304 or 316 L
Not applicable
coated with a PVC + PET film of total thickness 130 μm
0,6
* standard facing Standard colour : iceberg white (close to RAL 9010) NB: on request, the two facings can be of different materials on inside and outside faces (aspect, colour and/or thickness)
Metallic profile for passage of cables. Panel profiles
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
02-03-1
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
4
Partition SM60 Metal coatings and mineral wool core
GSP-0203-E/C
Technical characteristics
Vertical panel
Thickness
60 mm 2.36’’
0,20 m 0.65’ ; 0,25 m 0.82’ ; 0,35 m 1.15’ ; 0,55 m 1.80’ ; 0,80 m 2.62’ ; 1,00 m 3.28
Widths
1,20 m 3.94’
Maxi. lengths
4 m 13.12’
6 m 19.68’
Thermal conductivity coefficient
λ = 0,041 W/m.°C 0.023 Btu.ft/h.ft².°F
Thermal transmission coefficient
Uc = 0,612 W/m 2 .°C 0.109 Btu/h.ft².°F
R-value
1,6
Acceptable resisting to buckling
≥ 210 kPa 30.46 PSI (2,1 daN/cm 2 30.45 lbf/sp.in )
Weight
17 kg/m 2 3.48 lbs/sq.ft (2 faces 0,6 mm 0.02’’ )
Tightness in whole partition with silicon joint
Qs ≤ 0,0027 m 3 /h.m 2 0.0088 ft3/h.ft² under ∆P = 50 Pa 0.007 PSI
Maximum acceptable loads in partition
Bending resistance, panels on 2 supports
Partition height (m)
2,50 8.20’
3,00 9.84’
3,50 11.48’
4,00 13.12’
≥ 4,50 14.76’
q (daN/m 2 )
75 15.67 lbf/ft²
55 11.49 lbf/ft²
42 8.78 lbf/ft²
30 6.27 lbf/ft²
20 4.18 lbf/ft²
Installation
Profiles integrated in the thickness of SM panels, allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full length grooves both sides of wall panels. A special feature without the link profile allows this partition to become removable panel by panel, thanks to stainless steel clips. Assembly
joint silicone
profile
stainless steel clips
Assembly between panels
Tightness - Silicon sealant (quality-label SNJF ; complies with FDA 21 CFR 175.105) - Polymer MS caulk
09-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
02-03-2
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
5
Partition SM60 Metal coatings and mineral wool core
GSP-0203-E/C
Reports and approvals
Fire reaction: Euroclass = A2-s1,d0 Flame spread index (ASTM E84-01) = Class 1 Class 0 (BS 476 part 6&7) Flame spread (BS 476 part 7) = Class 1 Fire spread index(BS 476 part 6) = 0,7
FM Global approval: FM Approvals (standard 4880) = Class 1
UL approval (cable routing) Safety E471046
Consult the data n°0112 «Reports and approvals».
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
02-03-3
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
6
Ceiling SM60 Metal coatings and mineral wool core
GSP-0204-E/C
The ceiling SM60 is designed for Ultra-Clean rooms that must be kept completely free of micro-biological contamination. This ceiling consists of non combustible modular panels of thickness 60 mm 2.36’’ , made of time-stable materials and no emitting particles. The SM60 ceiling, providing smooth surfaces easy to clean, is airtight and insulating.
Design
Core
Hydrophobic rock wool plates Density: 100 kg/m 3 (ceiling) 6.24 lb/ft 3 Fire class according to EN 13501-1: A1
folded edges
Glue : bi-components Polyurethane
profile
metal coating
rock wool core
Facings
Class according to XP P 34-301
Supports
Coatings according to NF EN 10169
Thicknesses (in mm)
coated with polyester 25 μm lacquer coated with PVDF 35 μm lacquer
0,5 0.02’’ 0,6* 0.02’’ 0,8 0.03’’
llla lVb
0,6 0,6
Steel sheet S280 GD, hot-dip galvanised Z225 (225g/m² of zinc on the 2 faces) or similar
coated with PVC 120 μm
Vc
coated with a complex of polyester lacquer and PET film of total thickness 55 μm
0,6
Vc
polished S4
0,6
0,8
Smooth stainless steel sheet of slight 304 or 316 L
Not applicable
coated with a PVC + PET film of total thickness 130 μm
0,6
* standard facing Standard colour : iceberg white (close to RAL 9010) NB: on request, the two facings can be of different materials on inside and outside faces (aspect, colour and/or thickness)
Metallic profile for passage of cables. Panel profiles
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
02-04-1
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
7
Ceiling SM60 Metal coatings and mineral wool core
GSP-0204-E/C
Technical characteristics
Ceiling panel
Thickness
60 mm 2.36’’
Widths
0,35 m 1.15’ ; 0,55 m 1.80’
1,20 m 3.94’
Maxi. lengths
4 m 13.12’
6 m 19.68’
Thermal conductivity coefficient
λ = 0,041 W/m.°C 0.023 Btu.ft/h.ft².°F
Thermal transmission coefficient
Uc = 0,612 W/m 2 .°C 0.109 Btu/h.ft².°F
R-value
1,6
Acceptable resisting to buckling
≥ 210 kPa 30.46 PSI (2,1 daN/cm 2 30.45 lbf/sp.in )
Weight
18 kg/m 2 3.48 lbs/sq.ft (2 faces 0,6 mm 0.02’’ )
Acceptable span in ceiling
Walkable(*)
Non walkable
Without opening
3,20 m 10.50’
-
2,40 m 7.87’
If panel with opening, between 2 panels without opening If majority of panels with one to two opening by panel If opening «nonstandard» or important frequency of opening
2,40 m 7.87’
3,20 m 10.50’
With opening
2,80 m 9.19’
2,00 m 6.56’
1,60 m 5.25’
2,40 m 7.87’
Span = distance between two suspension pieces, longways of panel.
Small sections can be cut out (width < 600 mm 1.96’ ) without compromising the safety of the ceiling. With «nonstandard» openings (width > 0,665 m 2.18’ and/or area > 0,45 m 2 4.84 ft² it is necessary to provide additional fastening joist. Loads take into account for measures = 60 daN/m 2 12.53 lbf/ft² (panel weight included, panel on 2 supports) + 150 daN 337.21 lbf (if accessible ceiling, concentrated load at any point of the ceiling).
(*) : The SM60 ceiling must not be considered as a technical platform. For maintenance, it supports the passage of one person.
09-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
02-04-2
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
8
Ceiling SM60 Metal coatings and mineral wool core
GSP-0204-E/C
Installation
Profiles integrated in the thickness of SM panels, enable the assembly of panels and the passage of cables. The system uses an aluminium key profile that is integrated in the grooves of the 4 sides of the ceiling panels. A metallic profile is integrated in the grooves in order to hang the ceiling panels to the building structure. Assembly
profile
Assembly between panels
Fixing system of ceiling
Tightness - Silicon sealant (quality-label SNJF ; complies with FDA 21 CFR 175.105) - Polymer MS caulk - Flexible sealant in closed cells reticulate polyethylene adhesive strips, density 50 kg/m 3 3.12 lb.ft 3 , in the form of adhesive strip (over the ceiling)
Reports and approvals
Fire reaction: Euroclass = A2-s1,d0 Flame spread index (ASTM E84-01) = Class 1 Class 0 (BS 476 part 6&7)
Flame spread (BS 476 part 7) = Class 1 Fire spread index(BS 476 part 6) = 0,7 FM Global approval : FM Approvals (standard 4880) = Class 1
UL approval (cable routing) Safety E471046
Consult the data n°0112 «Reports and approvals».
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
02-04-3
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
9
Partition ST60 Metal coating and aluminium honeycomb core
GSP-0205-E/B
The ST60 partition is designed for Ultra-Clean rooms that must be kept completely free of micro-biological contamination. This partition consists of non combustible modular panels of thickness 60 mm 2.36’’ , made of time-stable materials and no emitting particles. The ST60 partition, providing smooth surfaces easy to clean, is airtight and insulating.
Design
Core
Aluminium honeycomb, link Ø 19 mm 0.75’’ , metal strip thickness 50 μm (vertical panels) Alloy 3003 (EN 573 standard) Rustproof treatment
Density : 20 kg/m 3 1.24 lb/ft 3 (50 µ) Fire reaction : non combustible Resistance to compression : average value 270 kPa 39.16 PSI
Glue : bi-components Polyurethane
metal coating
folded edges
profile
aluminium honeycomb core
Facings
Class according to XP P 34-301
Supports
Coatings according to NF EN 10169
Thicknesses (in mm)
coated with polyester 25 μm lacquer coated with PVDF 35 μm lacquer
0,5 0.02’’ 0,6* 0.02’’ 0,8 0.03’’
llla lVb
0,6 0,6
Steel sheet S280 GD, hot-dip galvanised Z225 (225g/m² of zinc on the 2 faces) or similar
coated with PVC 120 μm
Vc
coated with a complex of polyester lacquer and PET film of total thickness 55 μm
0,6
Vc
polished S4
0,6
0,8
Smooth stainless steel sheet of slight 304 or 316 L
Not applicable
coated with a PVC + PET film of total thickness 130 μm
0,6
* standard facing Standard colour : iceberg white (close to RAL 9010) NB: on request, the two facings can be of different materials on inside and outside faces (aspect, colour and/or thickness)
Panel profiles Metallic profile for passage of cables.
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
10
Partition ST60 Metal coating and aluminium honeycomb core
GSP-0205-E/B
Technical characteristics
Panel
Thickness
60 mm 2.36’’
0,20 m 0.65’ ; 0,25 m 0.82’ ; 0,35 m 1.15’ ; 0,55 m 1.80’ ; 0,80 m 2.62’ ; 1,00 m 3.28’
Widths
1,20 m 3.94’
Maxi. lengths
4 m 13.12’
6 m 19.68’
- 10,7 kg/m 2 2.19 lbs/sq.ft (2 faces 0,5 mm 0.019’’ steel) - 6,9 kg/m 2 1.41 lbs/sq.ft (2 faces 0,67 mm 0.027’’ aluminium)
Weight
Tightness in whole partition with silicon joint
Qs ≤ 0,0027 m 3 /h.m 2 0.0088 ft3/h.ft² under ∆P = 50 Pa 0.007 PSI
Maximum acceptable loads in partition
Bending resistance, panels on 2 supports
Partition height (m)
2,50 8.20’
3,00 9.84’
3,50 11.48’
4,00 13.12’
≤ 5,80 19.03’
q (daN/m 2 )
75 15.67 lbf/ft²
55 11.49 lbf/ft²
42 8.78 lbf/ft²
30 6.27 lbf/ft²
20 4.18 lbf/ft²
Installation
Profiles integrated in the thickness of ST panels, allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full length grooves both sides of wall panels. A special feature without the link profile allows this partition to become removable panel by panel, thanks to stainless steel clips. Assembly
joint silicone profile
stainless steel clips
Assembly between panels
Tightness - Silicon sealant (quality-label SNJF ; complies with FDA 21 CFR 175.105) - Polymer MS caulk
09-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
11
Partition ST60 Metal coating and aluminium honeycomb core
GSP-0205-E/B
Reports and approvals
Fire reaction: Euroclass = A2-s1,d0
FM Global approval: FM Approvals (standard 4880) = Class 1
UL approval (cable routing) Safety E471046
Consult the data n°0112 «Reports and approvals».
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-3-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
12
Ceiling ST60 Metal coating and aluminium honeycomb core
GSP-0206-E/B
The ceiling ST60 is designed for Ultra-Clean rooms that must be kept completely free of micro-biological contamination. This ceiling consists of non combustible modular panels of thickness 60 mm 2.36’’ , made of time-stable materials and no emitting particles. The ST60 ceiling, providing smooth surfaces easy to clean, is airtight and insulating.
Design
Core
Aluminium honeycomb, link Ø 19 mm 0.75’’ metal strip thickness 70 μ (ceiling panel) Alloy 3003 (EN 573 standard) Rustproof treatment
Density : 28 kg/m 3 1.75 lb/ft 3 (70 µ) Fire reaction : non combustible Resistance to compression : average value 270 kPa 39.16 PSI
Glue : bi-components Polyurethane
metal coating
folded edges
profile
aluminium honeycomb core
Facings
Class according to XP P 34-301
Supports
Coatings according to NF EN 10169
Thicknesses (in mm)
coated with polyester 25 μm lacquer coated with PVDF 35 μm lacquer
0,5 0.02’’ 0,6* 0.02’’ 0,8 0.03’’
llla lVb
0,6 0,6
Steel sheet S280 GD, hot-dip galvanised Z225 (225g/m² of zinc on the 2 faces) or similar
coated with PVC 120 μm
Vc
coated with a complex of polyester lacquer and PET film of total thickness 55 μm
0,6
Vc
polished S4
0,6
0,8
Smooth stainless steel sheet of slight 304 or 316 L
Not applicable
coated with a PVC + PET film of total thickness 130 μm
0,6
* standard facing Standard colour : iceberg white (close to RAL 9010) NB: on request, the two facings can be of different materials on inside and outside faces (aspect, colour and/or thickness)
Panel profiles Metallic profile for passage of cables.
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
13
Ceiling ST60 Metal coating and aluminium honeycomb core
GSP-0206-E/B
Technical characteristics
Panel
Thickness
60 mm 2.36’’
Widths
0,35 m 1.15’ ; 0,55 m 1.80’
1,20 m 3.94’
Maxi. lengths
4 m 13.12’
6 m 19.68’
- 10,7 kg/m 2 2.19 lbs/sq.ft (2 faces 0,5 mm 0.019’’ steel) - 6,9 kg/m 2 1.41 lbs/sq.ft (2 faces 0,67 mm 0.027’’ aluminium)
Weight
Acceptable span in ceiling
Walkable(*)
Non walkable
Without opening
-
3,00 m 9.84’
5,00 m 16.40’
If panel with opening, between 2 panels without opening If majority of panels with one to two opening by panel If opening «nonstandard» or important frequency of opening
2,80 m 9.19’
4,00 m 13.12’
With opening
2,20 m 7.87’
3,00 m 9.84’
2,40 m** 7.87’
2,00 m** 6.56’’
Small sections can be cut out (width < 600 mm 1.96’ ) without compromising the safety of the ceiling. With «nonstandard» openings (width > 0,665 m 2.18’ and/or area > 0,45 m 2 4.84 ft² it is necessary to provide additional fastening joist. (*) : The ST60 ceiling must not be considered as a technical platform. For maintenance, it supports the passage of one person. Span = distance between two suspension pieces, longways of panel. Loads take into account for measures = 60 daN/m 2 12.53 lbf/ft² (panel weight included, panel on 2 supports) + 150 daN 337.21 lbf (if accessible ceiling, concentrated load at any point of the ceiling). 2.5kn/m2 with suspension centres at 1.2m x 1.8m
(**) To study case by case.
Summary of permissible loads in kN/m² Span L (m)
2
2,5
3
4
5
7,2 1619 lbf 6,0 1349 lbf 4,8 1079 lbf 4,12 926 lbf 3,60 809 lbf 2,88 647 lbf
4,17 937 lbf 3,47 780 lbf 2,78 624 lbf 2,38 535 lbf 2,08 467 lbf 1,67 375 lbf
1,76 395 lbf 1,46 328 lbf 1,17 263 lbf 1,00 224 lbf 0,88 197 lbf 0,70 157 lbf
0,90 202 lbf 0,75 168 lbf 0,60 134 lbf 0,51 114 lbf 0,45 101 lbf 0,36 81 lbf
L / 200 L / 240 L / 300 L / 350 L / 400 L / 500
14,06 3160 lbf 11,72 2634 lbf 9,38 2108 lbf 8,04 1807 lbf 7,03 1580 lbf 5,63 1265 lbf
Beam
09-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
14
Ceiling ST60 Metal coating and aluminium honeycomb core
GSP-0206-E/B
Installation
Profiles integrated in the thickness of ST panels, enable the assembly of panels and the passage of cables. A metallic profile is integrated in the grooves in order to hang the ceiling panels to the building structure. Assembly
joint silicone profile
Assembly between panels
Fixing system of ceiling
Tightness - Silicon sealant (quality-label SNJF ; complies with FDA 21 CFR 175.105) - Polymer MS caulk - Flexible sealant in closed cells reticulate polyethylene adhesive strips, density 50 kg/m 3 3.12 lb.ft 3 , in the form of adhesive strip (over the ceiling)
Reports and approvals
Fire reaction: Euroclass = A2-s1,d0
FM Global approval: FM Approvals (standard 4880) = Class 1
UL approval (cable routing) Safety E471046
Consult the data n°0112 «Reports and approvals».
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-3-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
15
Modular ceiling on steel frame PPM
GSP-0208-E/B
The modular ceiling is like a self-bearing ceiling composed of a frame posi � oned according to a regular woof and of stud work elements of di ff erent dimensions easily interchangeable
Characteris Ɵ cs
The modular ceiling, « ush technical oor» consists of a lacquered steel frame and ling panels. Panels are available in di ff erent types (thk. 60 mm 2.36’’ or 80 mm 3.15’’ , mineral wool or aluminium honey comb core and di ff erent claddings) full or cut for installa � on of terminal parts of air treatment, light � ngs, etc... Dimensions or modules are on request with a maximum wide for panel of 1,20 m 3.94’ . This extremely exible concept allows to t all con gura � on. It can support permanent loads, as HVAC terminals... Uniform load allowed for de ec � on 1/250 th on length: - PPM60 panels of thickness 60 mm 2.36’’ mineral wool or aluminium honey comb core : above 150 daN/m² (1,5 kN/m²) 31 lbf/ Ō ² - PPM80 panels of thickness 80 mm 3.15’’ mineral wool core : above 150 daN/m² (1,5 kN/m²) 31 lbf/ Ō ² - PPM80 panels of thickness 80 mm 3.15’’ aluminium honey comb core : above 250 daN/m² (2,5 kN/m²) 52 lbf/ Ō ²
Mechanical resistance superior than 5 KN /m². Thermal insula � on : depending of the core and thickness Fire reac � on : class A2,s1-d0 class 0/BS476 part 6&7
Non contractual document - Dagard reserves the right to modify its products without no Ɵ ce.
29-01-2020
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
16
Technical panel
GSP-0210-E/B
The technical panel is a specific panel with a hollow core allowing a vertical passage for fluids and wiring.
sockets not supplied
Technical characteristics
The technical panel consists of two 6 mm 0.236’’ thick panels assembled in a rigid frame. It is flush mounted on partitions of Ultra- Clean line. One of the two sides is held in place by two magnetic strips and can be easily dismounted using suction cups as a removable cover. This cover can be divided up into several superposed elements. Width 400 mm 15.75’’ Available area 350 x 45 mm 13.78’’ x 1.77’’ over the entire height Heights 2400 mm 7.87’ , 3000 mm 9.84’ , 4000 mm 13.12’
external face
internal face
external face
internal face
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
17
Technical panel
GSP-0210-E/B
Note
Technical panels can be customized in factory for fluid inlets and outlets in sealed manner.
Example of adaptation: Stainless steel welded pipes at top end of the technical panel for cables passage and ulterior sealing.
09-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
18
Electrical race way
GSP-0213-E/B
The electrical raceway enables the passage of cables and accessories gathering between two panels of thickness 60 mm 2.36’’ from the Ultra-Clean line.
Description
The support and the cover are in lacquered aluminium, of width 100 mm 3.93’’ , of thickness 60 mm 2.36’’ , of basis length of 4 m 13.12’’ with a flat T-bracket for the mounting on adjustable belt. As the cover is fixed last, the cables can be set up after the partition mounting. All is totally recessed in the partition thickness and is flush on the two sides without visible fixings.
Technical characteristics
The removable cover enables to integrate different electrical accessories on semi-flush or flush way. - power socket, RJ45,... - switch - push button, lights,... - signal lamps
The electrical race way could be divided strong current-weak current. Openings, only on one part of the cover, are possible in factory or on site. Installation is the same as mullion mounting.
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
19
Electrical race way
GSP-0213-E/B
Option - Equipment set on factory
Electrical accessories are usually not provided with the race way, however, it is possible to prepare in factory pre equipped raceways, where accessories and wiring are integrated and sealed.
NB : these raceways can be used for passage of different fluids (air, gas, ...) example of installation
09-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
20
Mullion for removable area
GSP-0214-E/B
The technical panel allows to realise a removable zone in a 60 mm 2.36’’ thick partition made with panel of Ultra-Clean line. The removable area is useful for set up machines in construction phase and facilitate the maintenance or the future evolution of the process.
Design
The removable mullion consists of aluminium profiles. It can be used on adjustable metal belt or in U-profile for a removable area of one or several panels. It consists of : - a profile - a cover - a locking pawn Dimensions : - width 100 mm 3.94’’ - thickness 60 mm 2.36’’ - length 4 m 13.12’
Possible to put a finishing sheet
locking pawn
locking pawn
Machining for installation on adjustable belt
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
21
Connections for panels SI-SM-ST-SL-SA
GSP-0217-E/B
The connections of SI, SM, ST, SL, SA panels between themselves, with the floor or with the ceiling are adapted to the environment cleaning and decontamination restrictions the more strict.
Link with floor
By means of an adjustable metallic belt
A coving profile fillet is available as an option to provide support for floor upsweeps (PVC or resin). On the outside face, a plinth can be installed. The adjustable metallic belt enables the level to be adjusted while providing for a 5 mm 0.02’’ undercut here and there to enable the floor to be flush with the partition.
Dimensions : 80 (-10 +30) x 50 mm
3.15’’ (-0.39’’+1.18’’) x 1.97’’
plinth
PVC or resin floor
coving section or support
belt
By U-shaped piece
Partition can be linked to the floor with a lacquered aluminium or PVC U-profile, 60 mm 2.36’’ . A plinth on one side or on each side of the partition ensures the finish.
Principle: Installation of U-profile on finished floor.
plinthe
floor covering
U
Non contractual document - Dagard reserves the right to modify its products without notice.
09-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
22
Connections for panels SI-SM-ST-SL-SA
GSP-0217-E/B
Junctions between vertical panels
Junction at coving profile
angle coving section
angle coving section
angle coving section
outside angle bracket
semi-flush aluminium angle
flush aluminium angle
With a complement profile
With semi-flush angle post
With a flush angle post
Junction in partition
aluminium U-profile
inside aluminium L-profile
silicone
angle coving section
silicone
With PVC, aluminium, or stainless steel angle coving section
With aluminium U-profile
With aluminium L-profile
Junctions between ceilings and partitions
Support screw of vertical panels
Support angle bracket Silicone
Silicone
Silicone
Angle coving section
Silicone
Angle coving section
Support angle bracket
Junction ceiling to partition with load-bearing support on partition
Partition under ceiling junction by direct screwing
Partition under ceiling junction with fixing by angle coving section
09-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
23
Airtight double flush glazing
GSP-0220-F/B
Glazings are monobloc elements of thickness 60 mm 2.36’’ made of two laminated glasses mounted flush on a black aluminium profile with tightness on the periphery. They can be incorporated into walls (SI, SM, ST, SL) on site.
Application
These glazings can be used in premises where the relative humidity not exceeded 75% and with a temperature between +10°C 50°F and + 40 °C 104°F . The use of 100 mm 3.94’’ wide mullions increases the glazed surface (SI, SM range).
Glazing between 2 panels (SI/SM/ST/SL)
Characteristics
Glazings are bi-glasses made of black (RAL 9005) aluminium profile on which is bonded 2 laminated glasses 44.2 (according to the standard NF EN14449) with 2 peripheral inserts (containing molecular riddle or dryer). A silicon joint is extruded between glasses and aluminium profile in order to ensure the tightness, leaving the black (RAL 9005) peripheral aluminium profile visible. This profile enables the assembly between panels or glazings. A decompression valve can be set on glazings send by plane or mounted at more than an altitude of 1100 m 3609’ . Weight 47 kg/m² 9.63 lb/f 2 Coefficient U 2,66 W/m².k
Standard dimensions
Height (B) x Width (A) (mm) 798 x 798 2.62’ x 2.62’ 998 x 798 3.27’ x 2.62’ 1198 x 798 3.94’ x 2.62’
998 x 998 3.27’ x 3.27’ 1198 x 998 3.94 x 3.27’ 1198 x 1198 3.94’ x 3.94’
Other dimensions on request.
Non contractual document - Dagard reserves the right to modify its products without notice.
29-09-2021
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
24
Airtight double flush glazing
GSP-0220-F/B
Installation
Glazings are incorporated on site into SI, SM, ST or SL walls or between panels, spandrel and impost. A silicon joint assures the tightness between juxtaposed flush elements.
Mullion between glazings
Using mullions enables to increase the glazing surface.
The lacquered aluminium profiles are put between glazings in order to keep the partition rigidity. They can be used for the cable passage.
Variant with integrated blind only for glazings with thickness 60 mm 2.36’’
For glazings of thickness 60 mm 2.36’’ , it is possible to integrate white Venitian blinds, manuals or automatics, and adjustable. In manual control with rod or thin cord.
In automatic, control with remote control or button.
Glazed with inactinic film
Colored safelight films absorb light radiation between 300 and 570 nanometers in particular ultra violet radiation. They are used for protection against light and UV in production and control workshops, for example, for sensitive electronic equipment.
Up to 4 films can be stacked to obtain the performance required. The films are inserted between the glass during the manufacturing process of the glass. To be study case by case.
29-09-2021
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
25
Double flush door sheet leaf 60 Flush frame for panels of thickness 60 mm 2.36’’ , aluminium honey comb or mineral wool core GSP-0224-E/B
Service door with flush door frame on the 2 sides of the partition. The leaf, double flush, consists in aluminium honeycomb or mineral wool core bonded between 2 metallic facings.
Technical characteristics
Leaf • 1 or 2 leaves thickness 60 mm 2.36’’ • sandwich structure • aluminium honey comb or mineral wool core and aluminium structure profiles • smooth galvanised steel sheet 8/10 th 0.031’’ welded mechanical and painted with epoxy-polyester powder, heat-cured, iceberg white coloured (close to RAL 9010), options : colours according to the chart (GSP-1208) Door frame • one-piece double flush frame for panels of thickness 60 mm 2.36’’ • lacquered aluminium frame, heat-cured epoxy-polyester powder coating Options • stainless steel door frame • lifting impost 630 2.07’ , 730 2.39’ or 830 2.72’ mm for door 2040 x 1660 mm 6.69’ x 5.44’ and 2040 x 2060 mm 6.69’ x 6.76’ Left or right opening.
Tightness Closed profile sealant, 10 mm 0.39’’ trimming at the bottom of the door.
standards equipment
options
see data N°
adjustable stainless steel finishing aluminium hinges
adjustable
white
lacquered
GSP-0902-E/B
aluminium hinges
stainless steel hinges (no adjustable)
coloured PVC handle with european profile lock (single keyway) stainless steel handle with european profile lock (single keyway) white PVC pull handle (without lock) with push plate stainless steel pull handle (without lock) with push plate
white PVC handle with cylinder-type safety lock (single keyway)
GSP-0901-E/B
stamped stainless steel strike
panic push bar
GSP-0903-E/B
doors with 1 or 2 leaves
floor gasket
GSP-0906-E/B
sweeper gasket door stop
GSP-0905-E/B GSP-0904-E/B
wall mounting door closer
double flush vision panel 640 x 350 mm 2.10’ x 1.15’ , 800 x 500 mm 2.62’ x 1.64’ , 1000 x 500 mm 3.28’ x 1.64’
GSP-0920-E/B
grey PVC kick plate, height 850 mm 2.79’ on 1 or 2 faces
GSP-0911-E/B GSP-0912-E/B GSP-0914-E/B to GSP-0919-E/B GSP-0907-E/B GSP-0904-E/B
stainless steel sheet kick plate, height 850 mm 2.79’ on 1 or 2 faces
recessed magnetic lock airlock management
lever bolt top and bottom on half fixed leaf
doors with 2 leaves
closing selector
Non contractual document - Dagard reserves the right to modify its products without notice.
11-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
26
Double flush door sheet leaf 60 Flush frame for panels of thickness 60 mm 2.36’’ , aluminium honey comb or mineral wool core GSP-0224-E/B
Dimensions
clear opening
frame width
designation H x W 2040 x 630 80’’ x 25’’ 2040 x 830 80’’ x 33’’ 2040 x 930 80’’ x 37’’ 2040 x 1030 80’’ x 41’’ 2040 x 1130 80’’ x 45’’ 2040 x 1260 80’’ x 50’’ 2040 x 1460 80’’ x 58’’ 2040 x 1660 80’’ x 65’’ 2040 x 1860 80’’ x 73’’ 2040 x 2060 80’’ x 81’’
clear opening H x W 2039 x 609 80’’ x 24’’ 2039 x 809 80’’ x 32’’ 2039 x 909 80’’ x 36’’ 2039 x 1009 80’’ x 40’’ 2039 x 1109 80’’ x 44’’ 2039 x 1244 80’’ x 49’’ 2039 x 1444 80’’ x 57’’ 2039 x 1644 80’’ x 65’’ 2039 x 1844 80’’ x 73’’ 2039 x 2044 80’’ x 80’’
door frame H x W 2135 x 801 84’’ x 31’’ 2135 x 1001 84’’ x 39’’ 2135 x 1101 84’’ x 43’’ 2135 x 1201 84’’ x 47’’ 2135 x 1301 84’’ x 51’’ 2135 x 1436 84’’ x 56’’ 2135 x 1636 84’’ x 64’’ 2135 x 1836 84’’ x 72’’ 2135 x 2036 84’’ x 80’’ 2135 x 2236 84’’ x 88’’
designation H x W 2240 x 630 88’’ x 25’’ 2240 x 830 88’’ x 33’’ 2240 x 930 88’’ x 37’’ 2240 x 1030 88’’ x 41’’
clear opening H x W 2239 x 609 88’’ x 24’’ 2239 x 809 88’’ x 32’’ 2239 x 909 88’’ x 36’’ 2239 x 1009 88’’ x 40’’
door frame H x W 2335 x 801 92’’ x 31’’ 2335 x 1001 92’’ x 39’’ 2335 x 1101 92’’ x 43’’ 2335 x 1201 92’’ x 47’’
designation H x W
clear opening H x W
door frame H x W
(mm)
2440 x 930 96’’ x 37’’ 2440 x 1030 96’’ x 41’’
2439 x 909 96’’ x 36’’ 2439 x 1009 96’’ x 40’’
2535 x 1101 99’’ x 43’’ 2535 x 1201 99’’ x 47’’
1 leaf
2240 x 1260 88’’ x 50’’
2239 x 1244 88’’ x 49’’
2335 x 1436 92’’ x 56’’
2239 x 1644 88’’ x 65’’
2335 x 1836 92’’ x 72’’
2440 x 1660 96’’ x 65’’
2439 x 1644 96’’ x 65’’
2535 x 1836 99’’ x 72’’
2240 x 1660 88’’ x 65’’
2 leaves
2335 x 2236 92’’ x 88’’
2240 x 2060 88’’ x 81’’
2239 x 2044 88’’ x 80’’
2440 x 2060 96’’ x 81’’
2439 x 2044 96’’ x 80’’
2535 x 2236 99’’ x 88’’
Permeability
Air leakage rate for single leaf hinged door with floor gasket Nota : - a door is under pressure when the action of the air tends to stick the leaf on the door frame - a door is in vacuum when the action of the air tends to spread the leaf of the door frame The permeability of the double flush doors with floor gasket is note in report n°2612115 made by CETIAT.
pressure depression
pressure (Pa)
11-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
27
Double flush door glazed leaf 60 mm 2.36’’ Flush frame for panels of thickness 60 mm 2.36’’ , aluminium frame and double laminated glazing
GSP-0226-E/B
Service door with flush frame on the 2 sides of the partition. The leaf, double flush, consists in lacquered aluminium frame and a laminated double glazing of thickness 60 mm 2.36’’ .
Technical characteristics
Leaf • 1 or 2 leaves thickness 60 mm 2.36’’ • lacquered aluminium structure • filling with a double glazing : 2 laminated glasses 33.2 Door frame • one piece flush frame for panels of thickness 60 mm 2.36’’ • lacquered aluminium frame, heat-cured epoxy-polyester powder paint option : stainless steel frame Tightness Sealant on 3 sides and 10 mm 0.39’’ trimming at the bottom of the door.
Left or right opening.
standards equipment
options
see data N°
adjustable white lacquered aluminium hinges
adjustable stainless steel finishing aluminium hinges
GSP-0902-E/B
coloured PVC handle with european profile lock (single keyway) stainless steel handle with european profile lock (single keyway) white PVC pull handle (without lock) with push plate stainless steel pull handle (without lock) with push plate
white PVC handle with cylinder-type safety lock (single keyway)
GSP-0901-E/B
stamped stainless steel strike
doors with 1 or 2 leaves
panic push bar
GSP-0903-E/B
floor gasket
GSP-0906-E/B
sweeper gasket door stop
GSP-0905-E/B GSP-0904-E/B GSP-0914-E/B to GSP-0919-E/B GSP-0907-E/B GSP-0904-E/B
wall mounted door closer closing detection contact recessed magnetic lock airlock management
lever bolt top and bottom on half fixed leaf
doors with 2 leaves
closing selector
Non contractual document - Dagard reserves the right to modify its products without notice.
11-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
28
Double flush door glazed leaf 60 mm 2.36’’ Flush frame for panels of thickness 60 mm 2.36’’ , aluminium frame and double laminated glazing
GSP-0226-E/B
Dimensions
clear opening
frame width
(mm)
designation H x W 2040 x 830 80’’ x 33’’ 2040 x 930 80’’ x 37’’ 2040 x 1030 80’’ x 41’’ 2040 x 1260 80’’ x 50’’ 2040 x 1460 80’’ x 58’’ 2040 x 1660 80’’ x 65’’ 2040 x 1860 80’’ x 73’’ 2040 x 2060 80’’ x 81’’
clear opening H x W 2039 x 809 80’’ x 32’’ 2039 x 909 80’’ x 36’’ 2039 x 1009 80’’ x 40’’ 2039 x 1244 80’’ x 49’’ 2039 x 1444 80’’ x 57’’ 2039 x 1644 80’’ x 65’’ 2039 x 1844 80’’ x 73’’ 2039 x 2044 80’’ x 80’’
door frame H x W 2135 x 1001 84’’ x 39’’ 2135 x 1101 84’’ x 43’’ 2135 x 1201 84’’ x 47’’ 2135 x 1436 84’’ x 56’’ 2135 x 1636 84’’ x 64’’ 2135 x 1836 84’’ x 72’’ 2135 x 2036 84’’ x 80’’ 2135 x 2236 84’’ x 88’’
1 leaf
2 leaves
Permeability
Nota : - a door is under pressure when the action of the air tends to stick the leaf on the door frame - a door is in vacuum when the action of the air tends to spread the leaf of the door frame
Air leakage rate for single leaf hinged door with floor gasket The permeability of the double flush doors with floor gasket is note in report n°2612115 made by CETIAT.
pressure depression
pressure (Pa)
11-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
29
Tight sliding door Flush frame for panels of thickness 60 mm 2.36’’ , leaf 40 mm 1.57’’ aluminium honey comb core
GSP-0228-E/B
Sliding door with flush frame on one side of the partition. The leaf consists in aluminium honeycomb core bonded between 2 metallic facings. Sliding system with ramps and tightness on the 4 sides. Door easy to clean for an use in all clean rooms.
Technical characteristics
Leaf • 1 leaf of thickness 40 mm 1.57’’ • sandwich structure with a reinforced frame integrated • aluminium honey comb core • facing (colour according to the chart) : smooth galvanised steel sheet 6/10 th and painted with epoxy-polyester powder, heat-cured. • mono component polyurethane glue Option : • door with 2 leaves • automatism
Door frame • one-piece frame for panels of thickness 60 mm 2.36’’ • galvanised steel Z225 frame, heat-cured epoxy-polyester powder coating.
Tightness • airtight peripheral joint on the 4 sides Left or right opening.
Sliding system: The manual system consists in a track fixed directly on the frame with integrated ramps and butts. Aluminium track cover, easy to clean and designed to receive, without modification, an automatism. White colour close to RAL 9010.
standards equipment
options
see data N°
aluminium pull handle outside recessed pull handle inside anodized aluminium track with lacquered aluminium cover track bottom door guides
stainless steel pull handle (without lock) on external side
GSP-0908-E/A
door with 1 leaf
double flush vision panel 640 x 350 mm 2.1’ x 1.15’ , 800 x 500 mm 2.6’ x 1.6’ , 1000 x 500 mm 3.3’ x 1.6’
GSP-0920-E/A
grey PVC kick plate, height 850 mm 2.8’ on 1 or 2 faces
GSP-0911-E/B GSP-0912-E/B GSP-0910-E/A GSP-0913-E/A
stainless steel sheet kick plate, height 850 mm 2.8’ on 1 or 2 faces
automatism electric bolt
Non contractual document - Dagard reserves the right to modify its products without notice.
11-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
30
Tight sliding door Flush frame for panels of thickness 60 mm 2.36’’ , leaf 40 mm 1.57’’ aluminium honey comb core
GSP-0228-E/B
Dimensions
overall H x W
overall H x W
overall H x W
clear opening H x W 2200 x 950 86’’ x 37’’ 2200 x 1200 86’’ x 47’’ 2200 x 1400 86’’ x 55’’ 2200 x 1600 86’’ x 63’’ 2200 x 1800 86’’ x 70’’ 2200 x 2000 86’’ x 78’’
clear opening H x W 2400 x 950 94’’ x 37’’ 2400 x 1200 94’’ x 47’’ 2400 x 1400 94’’ x 55’’ 2400 x 1600 94’’ x 63’’ 2400 x 1800 94’’ x 70’’ 2400 x 2000 94’’ x 78’’
clear opening H x W 2000 x 950 78’’ x 37’’ 2000 x 1200 78’’ x 47’’ 2000 x 1400 78’’ x 55’’ 2000 x 1600 78’’ x 63’’ 2000 x 1800 78’’ x 70’’ 2000 x 2000 78’’ x 78’’
(mm)
2345 x 2118 92’’ x 83’’ 2345 x 2618 92’’ x 103’’ 2345 x 3018 92’’ x 119’’ 2345 x 3418 92’’ x 134’’ 2345 x 3818 92’’ x 150’’ 2345 x 4218 92’’ x 166’’
2545 x 2118 100’’ x 83’’ 2545 x 2618 100’’ x 103’’ 2545 x 3018 100’’ x 119’’ 2545 x 3418 100’’ x 134’’ 2545 x 3818 100’’ x 150’’ 2545 x 4218 100’’ x 166’’
2745 x 2118 108’’ x 83’’ 2745 x 2618 108’’ x 103’’ 2745 x 3018 108’’ x 119’’ 2745 x 3418 108’’ x 134’’ 2745 x 3818 108’’ x 150’’ 2745 x 4218 108’’ x 166’’
1 leaf
Overall = 2 x leaf width + 90 mm
clear opening width = LPL width leaf = LPL +60 door frame width = LPL+180
bottom guides easily washable
Thin and easy to clean rail cover
gasket easily washable
11-07-2019
Non contractual document - Dagard reserves the right to modify its products without notice.
-2-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
31
Tight sliding door Flush frame for panels of thickness 60 mm 2.36’’ , leaf 40 mm 1.57’’ aluminium honey comb core
GSP-0228-E/B
Permeability
The air permeability of the sliding doors has been measured and recorded in CETIAT test report N°1014119. Permeability of a sliding door in m 3 /h depending on pressure or depression.
Airtightness test of Dagard sliding door with single seal
Airtightness test of Dagard sliding door with double seal
positive pressure test suction pressure test
positive pressure test suction pressure test
Pressure level (in Pa)
Pressure level (in Pa)
Nota : - a door is under pressure when the action of the air tends to stick the leaf on the door frame - a door is in vacuum when the action of the air tends to spread the leaf of the door frame
Use recommendation
Automatic tight sliding doors don’t comply the CO48 regulation, requiring an automatic opening, in case of lack of power, by an independent mechanical solution. We propose as, an option, an opening by safety battery.
Non contractual document - Dagard reserves the right to modify its products without notice.
11-07-2019
-3-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
32
Glazed and tight sliding door Flush door frame for panels of thickness 60 mm 2.36’’ , leaf 40 mm 1.57’’ aluminium frame
GSP-0230-E/B
Sliding door with flush frame flush on one side of the partition. The leaf consists in lacquered aluminium door frame and a double laminated glazing of thickness 40 mm 1.57’’ . Sliding system with ramps and tightness on the 4 sides. Door easy to clean for an use in all clean rooms.
Technical characteristics
Leaf • 1 leaf of thickness 40 mm 1.57’’ • lacquered aluminium structure • filling with a double flush glazing of thickness 40 mm 1.57’’ made of 2 laminated glasses 33-2. Option : • door with 2 leaves • automatism
Door frame • one-piece frame for panels of thickness 60 mm 2.36’’ • galvanised steel Z225 frame, heat-cured epoxy-polyester powder coating.
Left or right opening.
Tightness • airtight peripheral joint
Sliding system: The manual system consists in a track fixed directly on the frame with integrated ramps and butts. Aluminium track cover, easy to clean and designed to receive, without modification, an automatism. White colour close to RAL 9010.
standards equipment
options
see data N°
aluminium pull handle outside recessed pull handle inside anodized aluminium track with lacquered aluminium cover track bottom door guides
door with 1 leaf
automatism
GSP-0910-E/B
Non contractual document - Dagard reserves the right to modify its products without notice.
11-07-2019
-1-
DAGARD - Route du Stade - 23600 Boussac - FRANCE
info@dagard.com - www.dagard.com
33
Page 1 Page 2 Page 3 Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 Page 10 Page 11 Page 12 Page 13 Page 14 Page 15 Page 16 Page 17 Page 18 Page 19 Page 20 Page 21 Page 22 Page 23 Page 24 Page 25 Page 26 Page 27 Page 28 Page 29 Page 30 Page 31 Page 32 Page 33 Page 34 Page 35 Page 36 Page 37 Page 38 Page 39 Page 40 Page 41 Page 42 Page 43 Page 44 Page 45 Page 46 Page 47 Page 48 Page 49 Page 50 Page 51 Page 52 Page 53 Page 54 Page 55 Page 56 Page 57 Page 58 Page 59 Page 60 Page 61 Page 62 Page 63 Page 64 Page 65 Page 66 Page 67 Page 68 Page 69 Page 70 Page 71 Page 72 Page 73 Page 74 Page 75 Page 76 Page 77 Page 78 Page 79 Page 80 Page 81 Page 82 Page 83 Page 84 Page 85 Page 86 Page 87 Page 88 Page 89 Page 90 Page 91 Page 92 Page 93 Page 94 Page 95Made with FlippingBook - professional solution for displaying marketing and sales documents online