Viega UK 2023-24 Brochure

Range overview

Flow-optimised press connector system with press connectors and pipes made of stainless steel 1.4401. Press connectors for protecting the sealing element equipped with cylindrical pipe guide. Press connectors from d64.0 with stainless steel cutting ring to ensure the mechanical strength of the connection. For protection pipes are equipped with pipe plugs. The pressing force is located before and behind the sealing element seat. Suitable for concealed and pre-wall installations of riser pipes and floor installations. Marking Manufacturer, pipe dimension, batch, yellow dot on press end, yellow rectangle with inscription »Gas MOP 5 / GT5« for Sanpress Inox G connectors, yellow rectangle with inscription »Gas MOP 5 / GT1« for Profipress G connectors made of gunmetal, yellow pipe plug, detachable orange label as press indicator from d64.0 Press connector with SC-Contur Inadvertently unpressed connections are noticed immediately during a leakage test. Viega guarantees the detection of unpressed connections in the following pressure ranges with compressed air or inert gases: Min. air pressure: 22 hPa / 2.2 kPa / 22 mbar / 0.3 PSI Max. air pressure: 0.3 MPa / 300kPa / 3 bar / 43.5 PSI Sealing elements HNBR (hydrogenated acrylonitrile butadiene rubber), yellow, pre-assembled

Operating conditions gas and liquid gas installations Operating temperature -20 °C to +70 °C (-4 °F to +158 °F) Operating pressure max. 0.5 MPa / 5 bar / 72.5 PSI Operating pressure at HTB requirements 650°C (1202 °F)/30 minutes max. 0.5 MPa (5 bar; 72.5 PSI) Operating conditions heating oil and diesel fuel installation Operating temperature max. 40 °C / 104 °F Operating pressure -0.05 to +0.5 MPa (-0.5 to +5 bar / -7.25 to +72.5 PSI)

Press connector material Stainless steel 1.4401

Subject to change without prior notice! Latest Z- and installation dimensions as well as further technical information can be found on the Viega website and have to be checked before purchase, planning, construction work and use. Our products are continuously optimised. This product description contains important information on choice of product and system, mounting, commissioning as well as intended use and, if required, on maintenance measures. This information on products, their features and application techniques is based on currently valid standards in Europe (e.g. EN) and/or in Germany (e.g. DIN/DVGW). Some passages in the text may refer to technical regulations in Europe/Germany. These should be considered as recommen- dations for other countries where no corresponding national requirements exist. The relevant national laws, standards, regulations, directives and other technical provisions take priority over the German/European directives specified in this product description: The information herein is not binding for other countries and regions and should be understood as recommendation.

Dimensions d15–108.0

Tools The functional safety of Viega press connector systems depends primarily on the faultless condition of the press tools used. For the installation of press connections, Viega recommends the use of Viega press tools. Viega press tools have to be regularly maintained by authorised service partners.

Areas of application Natural gas/liquid gas

Heating oil Diesel fuel

Note The system components should be protected against high concentrations of chloride generated by both the medium and by external factors. Use of the system for areas of application and media other than those described must be agreed in consultation with Viega! Detailed information about applica- tions, restrictions and national standards and directives can be found in the product information, either printed or on the Viega website. Note – Standards and approvals Press connector system with press connectors and pipes in accordance with DIN EN 10088, DVGW Worksheet GW 541. Press connector approval for stainless steel in accordance with DG-8531BR0333. Press connector approval for gunmetal in accordance with DG-8531BP0069. Gases in accordance with DVGW G 260 in gas installations in accordance with DVGW-TRGI 2018 (DVGW Worksheet G 600) / DVFG-TRF 2021. Liquid gases in the gas phase for domestic and commercial applications, tested in accordance with DVGW Worksheet G 5614. Piping for heating oil in accordance with DIN 51603 and piping for diesel fuel as suction and pressure line in accordance with DIN EN 590 in consideration of the General Building Approval Z-38.4‑184.

134

Made with FlippingBook - Online catalogs