STANDARD FEATURES of CONSTRUCTION

Pipe and Fitting Construction:

• Standard Fives-1001 Piping Specifications available upon request • Pipe sealant, Loctite PST (pipe sealant 127 withTeflon) • Oxygen use, see Bulletin 9526/27 • Other fluids, contact Engineering for information

Pipe Support Frames:

• Structural ASTM A36 carbon steel • Welding standards on Fives drawing 13-0277, per AWS, ANSI/ASME Sect. I, IV and IX

• Floor bracket bolt down mounting • Optional wall mounting upon request

Paint:

• Standard North American -1003 Surface Preparation and Protective Coatings Standard, available upon request • One coat of ANSI 49 Gray, low VOC, 3.5-5 mils wet thickness, high gloss, high solids air dry alkyd enamel

Electrical Construction:

• Standard North American -1000 Fuel Train Electrical Packaging Standard, available upon request • Per National Electric Code (NFPA 70), most recent edition • Wire = 14 Ga, 19 strand MTW 600 volt, T & B connectors • STOOW Cable with Brad Harrison mini-style connectors • Electrical NEMA rating determined by job

Quality Assurance:

• Pressure Test: All Systems assured leak-free prior to shipment at 1.5 times rated pressure or the maximum pressure allowed by all components. • Component Functionality Test: All components are cycled by normal actuation. • Continuity: All circuits are assured complete. • Tightness Testing: All safety shut-off valves are cycled and tested for tightness. • Documentation: Report of tests including description of tests performed. • Customers are welcome to view any phase of the quality assurance procedure, call for schedule.

Documentation:

• Quality assurance forms • Product literature • Assembly drawings and bills of materials • Electronic drawings and 3D models available upon request

The preceding represents “General Standards”, individual products may differ as the application and use require. Call Engineering for details. Fives North American Combustion, Inc. can review and consider customer specifications as requested in writing.

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.