Combustion Catalog | Fives North American

Specifications | Ignition Transformers

4065 TRANSFORMER SPECIFICATIONS (120 V)

4065-6N1-10A Family

Approvals: UL, CSA

No. of secondary terminals

PRIMARY

SECONDARY

Transformer Designation

-B ( ¼ ring tongue) -B ( ¼ ring tongue) 4085 Igniton cable req'd. (style)

Weight, lb

volts

volts

Enclosure

mA

hertz VA

4065-6N1-10A 4065-6N4-10A

120 120

60 60

250 250

10 000 10 000

22 22

1 1

10 25

None

12 x 12 NEMA 4

DIMENSIONS inches

High voltage terminal ¼ -20 thread

5 3⁄8

4 3⁄8

5 3⁄16

2 ½

4 5⁄8

3 7⁄8

7 7 7⁄8

¾ Conduit K.O. (both sides and on base plate)

5⁄16 x 10

Use 1/4" ring tongue connector for 4085 connector (type "B")

4065-6N1-5B Family

Approvals: UL

No. of secondary terminals

PRIMARY

SECONDARY

Transformer Designation

4085 Igniton cable req'd. (style)

Weight, lb

volts

volts

Enclosure

mA

hertz VA

4065-6N1-5B

120

60

250

5000

22

2

15

-A ( # 10ring tongue)

None

Note: This is a center tap ignition transformer, each secondary is 5,000V to ground but is 10,000 volts between secondary terminals. Center tap ignition transformers are intended for use with dual electrode igniters which are common for direct spark lighting of oil burners, such as the North American 5025-1 oil pilot. DIMENSIONS inches

3⁄8 x 2

4 15⁄16

6 ¼

2 9⁄16

4 7⁄8

6 7⁄8 7 5⁄8

3 3⁄8

5⁄16 x 8

¾ Conduit K.O. (both sides)

Use #10 ring tongue connector for 4085 connector (type "A")

Bulletin 4065/4066 Page 4