Specifications | Ignition Transformers

ADDITIONAL TRANSMFORMER SPECIFICATIONS

Approvals: UL & CSA

R130-5148 Half-Wave Ignition Transformer

terminals No. of secondary

Weight

Primary

4085 Igniton cable

Designation R130-5148 4065-Q624 Transformer

Secondary

volts hertz

VA

volts

lb

req'd (style)

Enclosure

120 50/60 66 120 50/60 66

10 000 10 000

1 1

3.0 8.0

Standard ( ¼ " Ø snap on) Standard ( ¼ " Ø snap on)

None

10 x 8 Nema 4

Prevents detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035, or C7044 Minipeeper® or C7061 Dynamic Self-Check Ultraviolet Flame Detectors. Ignition spark and ultraviolet detector are synchronized by the alternating current supply voltage; spark occurs on one half of the ac cycle and detector operates on the opposite half cycle.

— Ignites gas pilots with spark gaps up to 1/4 inch (6 millimeters) in length. — Maximum High Voltage Lead Length: 15 ft. (4.6 m) — Ambient Temperature Range: -40°F to +125°F (-40°C to +52°C). — Maximum Ambient Humidity: 95 percent RH.

The spark produced by this transformer is not as strong as the larger 4065/4066 transformers. They work better with short spark plugs than with long electrode igniters.

4 1⁄8

High voltage ¼ Ø snap-on terminal

4 1⁄8

5 ¼

1 ¼

4 ¼

5 15⁄16

19⁄64

K.O. for 1/2" Conduit

6 ¾

Use standard ¼ " Ø snap-on connector for 4085 connector (type "C")

or a 90° spark plug boot (type "N")

Bulletin 4065/4066 Page 7