Specifications | Ignition Transformers
ADDITIONAL TRANSMFORMER SPECIFICATIONS
Approvals: UL & CSA
R130-5148 Half-Wave Ignition Transformer
terminals No. of secondary
Weight
Primary
4085 Igniton cable
Designation R130-5148 4065-Q624 Transformer
Secondary
volts hertz
VA
volts
lb
req'd (style)
Enclosure
120 50/60 66 120 50/60 66
10 000 10 000
1 1
3.0 8.0
Standard ( ¼ " Ø snap on) Standard ( ¼ " Ø snap on)
None
10 x 8 Nema 4
Prevents detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035, or C7044 Minipeeper® or C7061 Dynamic Self-Check Ultraviolet Flame Detectors. Ignition spark and ultraviolet detector are synchronized by the alternating current supply voltage; spark occurs on one half of the ac cycle and detector operates on the opposite half cycle.
— Ignites gas pilots with spark gaps up to 1/4 inch (6 millimeters) in length. — Maximum High Voltage Lead Length: 15 ft. (4.6 m) — Ambient Temperature Range: -40°F to +125°F (-40°C to +52°C). — Maximum Ambient Humidity: 95 percent RH.
The spark produced by this transformer is not as strong as the larger 4065/4066 transformers. They work better with short spark plugs than with long electrode igniters.
4 1⁄8
High voltage ¼ Ø snap-on terminal
4 1⁄8
5 ¼
1 ¼
4 ¼
5 15⁄16
19⁄64
K.O. for 1/2" Conduit
6 ¾
Use standard ¼ " Ø snap-on connector for 4085 connector (type "C")
or a 90° spark plug boot (type "N")
Bulletin 4065/4066 Page 7