Combustion Catalog | Fives North American

Operation | Automatic Oil Shutoff Valves

OPERATION All electro-mechanical valves require a constant supply of electrical energy to their holding actuator solenoids. Once the solenoid is energized, the manual reset valve may be opened manually, or the automatic reset valve will automatically open. Interruption of electrical power causes an immediate "trip" of the valve to its normally-closed position. The swinging gate body has carefully machined sealing surfaces. Frequent use and cycling actually helps to keep the valve clean.

TEMPERATURE LIMITS All valves can handle fluid temperatures from –20°F (–28°C) to +250°F (+121°C). Ambient temperature limits vary. Any valve on this page us- ing dc voltage and all ½ " and ¾ " series 1517 Valves can handle ambient temperatures from –20°F (–28°C) to +125°F (+52°C). The other valves on this page handle ambient temperatures from –20°F (–28°C) to +140°F (+60°C).

Body Material

Gray Iron

Cast Steel

Top Assembly Sanctioned Service Sanctioned Service Function  

1517-01 1517-0 1517-1 1517-2

1517-01-S 1517-0-S 1517-1-S 1517-2-S

Automatic Reset

 Sanctioned series are sold for "clean fuel oils" and carry FM and CSA sanctions. They are approved for liquefied petroleum gases, #1 and #2 fuel oils, kerosene, JP-4 and preheated #4, #5, and #6 oils with maximum viscosity of 5000 SSU.

Available Sizes and Pressure Ratings

Maximum Inlet Pressure, psig 

Gray Iron Bodies

Cast Steel Bodies

Pipe Size

Body C v Flow Factor

Clean Gases & Oils

Clean Gases & Oils

inches

Special Service

Special Service

3.4 9.6

300 300 300 300

300 300 300 300

600 600 600 600

600 600 600 600

½ ¾

1

12 17

1 ¼

 Maximum operating pressure differential must not exceed the maximum inlet pressure.

Bulletin 1517 Page 3