Electrical Data | Automatic Oil Shutoff Valves

ELECTRICAL DATA for normally-closed valves

Automatic Reset Valves 1"-1¼" 1517

VALVE WIRING DIAGRAM

SWITCH CONTACT POSITIONS SHOWN WITH VALVE CLOSED

VCS-2

VOS-2

VOS-1

VCS-1

MOTORIZED VALVE ONLY SOLENOID

WARNING! VALVE MUST BE WIRED AS SHOWN

INTERNAL WIRING

MTR

FIELD WIRING

SPDT

SPDT

INDEPENDENT SOLENOID POWER SUPPLY (AC or DC)

DPDT

DPDT

L1-H L2-N AC-POWER SEE NAMEPLATE FOR VOLTAGE AND Hz.

SWITCH RATINGS Total connected load not to exceed 1700 VA SPDT DPDT Herm. Sealed

VOS-1

VOS-2

VCS-1

VCS-2

VALVE MODE

1-3

1-3 4-5 4-6

7-8

7-9

7-8

7-9 10-11 10-12

FULLY-SHUT INTERMEDIATE FULLY-OPEN

125 VAC - 15 AMP 250 VAC - 15 AMP 125 VDC - 0.5 AMP 250 VDC - 0.25 AMP

125 VAC - 10 AMP 250 VAC - 10 AMP 125 VDC - 0.3 AMP 250 VDC - 0.15 AMP

48 VAC - 1 AMP 125 VAC - 1 AMP 48 VDC - 3 AMP 125 VDC - 1 AMP

Automatic Reset Valves ½" and ¾" 1517

VALVE WIRING DIAGRAM

SWITCH CONTACT POSITIONS SHOWN WITH VALVE CLOSED

VCS-2

VOS-2

VOS-1

VCS-1

90 VDC

WARNING! VALVE MUST BE WIRED AS SHOWN

CLUTCH

SWITCH RATINGS Total connected load not to exceed 1800 VA SPDT DPDT 125 VAC - 15 AMP 125 VAC - 10 AMP 250 VAC - 15 AMP 250 VAC - 10 AMP 125 VDC - 0.5 AMP 125 VDC - 0.3 AMP 250 VDC - 0.25 AMP 250 VDC - 0.15 AMP

CLUTCH RECTIFIER CIRCUIT

SPDT

SPDT

DPDT

DPDT

AC-POWER INPUT L1-H L2-N

VALVE MODE

VOS-1

VOS-2

VCS-1

VCS-2

1-3

1-3 4-5 4-6

7-8

7-9

7-8

7-9 10-11 10-12

FULLY-SHUT INTERMEDIATE FULLY-OPEN

SEE NAMEPLATE FOR VOLTS, Hz, VA RATINGS.

Bulletin 1517 Page 5