ELECTRICAL DATA

Volt-ampere (VA) ratings All solenoid, circuit board, and motor ratings are shown in Table I. Total connected load on any valve should not exceed 2000 VA. This limitation includes the maximum consumption shown in Table I plus the VA consumption of external equipment powered by the auxiliary switches at any one time. TABLE I Valve VA Ratings Size (ac operation) Type (inches) Series Opening Holding ¾ -3 1518 22 22 Manual 6 1518 34 34 Reset 2 ½ -4 1518- -E 34 34 ¾ -3 1519 220 22 Motorized 2 ½ -4 1519- -E 232 34 4-6 1519- -X 376 8 Wiring Diagrams Each automatic shutoff valve includes one of the wiring diagrams shown below and on Page 4. Switch contacts are shown with the valve shut, unpowered. Wiring shown above the terminal strip is internal. Wiring below terminal strip is external (field), as required. All wires are number-coded as shown to match terminals. Termi- nals "2" and "DC" are neutral; all others are hot.

General

All standard shutoff valves are designed for operation on 115 V 60 Hz power supply. Optional voltages, Hz, direct current, or special switches, involve extra cost and extended delivery. Specify power characteristics when ordering. A solenoid or circuit board is energized whenever valve is powered. Holding current volt-amperes are continuous once energized. Motor on any 1519 Valve is powered only during the opening stroke. The normally closed contact of a limit switch breaks motor circuit when full-open position is reached. Flow begins within 1 second of powering. Full closure is complete within 1 second after de-energizing. Supply voltage must agree with valves nameplate voltage within -15%/+10% for proper operation.

Series 1519- -X only

Standard 120 V power input is converted by a circuit board (no solenoid) to 90 V dc output to a magnetic clutch that is energized whenever valve is powered. Circuit board components also act as a time delay, allowing 1⁄10 second response lag after main power interruption (this helps avoid nuisance shutdowns).

WARNING: Do not attempt field repair of valve body, top assembly, or motor drive unit. Any alterations could be dangerous, and will void all warranties.

TYPICAL WIRING FOR ALL VALVES EXCEPT 1519- -X

SWITCH CONTACT POSITIONS SHOWN WITH VALVE CLOSED

VALVE CLOSED SWITCH (FM PROOF OF CLOSURE)

VALVE OPEN SWITCH

MOTORIZED VALVE ONLY SOLENOID

GROUND

INTERNAL WIRING

MTR

WARNING: VALVE MUST BE WIRED AS SHOWN

DC+ DC– 1

2

3

4

5

6

11

12

7

8 9 10

FIELD WIRING

L1 HOT

L2 NEU

INDEPENDENT SOLENOID POWER SUPPLY (AC or DC)

DPDT

SPDT

AC POWER SEE NAME PLATE FOR VOLTAGE AND HZ

TYPICAL SWITCH ACTION (O = Open contacts; X = Closed contacts between indicated terminals.) Valve Valve Open Switch Closed Switch Valve Position 1-3 4-5 4-6 7-8 7-9 Fully Closed O X O X O Intermediate O X O O X Fully Open X O X O X

SWITCH RATINGS Total connected load not to exceed 1700 VA including values from Table I SPDT DPDT 125 V ac- 15 amp 125 V ac- 10 amp 250 V ac- 15 amp 250 V ac- 10 amp 125 V dc- 0.5 amp 125 V dc- 0.3 amp 250 V dc- 0.25 amp 250 V dc- 0.15 amp

Bulletin 1518/1519 Page 5