Sheet 1597-5 Page 2

• Make sure the O-rings are clean and in good condition. • Remove the G 1⁄8 plugs from the port 1 and port 1 of the valve with a 3 mm hex key wrench. • Make sure that the surface is clean and in good condition. If neces- sary clean the surfaces. • Mount the Valve Proving Device onto the ports using the M4  15 mm socket head screws. • Make sure that the O-rings are located in the grooves. • Tighten the screws snugly, not exceeding 22 lb-in. • Perform a leak test to verify that no leakage occurs around the O- rings. • Disconnect all power to the Valve Proving Device before beginning the wiring to prevent electrical shock and equipment damage. • All wiring must comply with local electrical codes, ordinances, and regulations.

L2

L1

Main Power 120 Vac 60 Hz

VPS 504

N

L1

ALARM

T3

Alarm

RUN

1CR

T5

Flame Safeguard

Blower

Burner Start

1CR1

Low Gas

High Gas

Pilot Valve

L1

SSOV

Alarm

Air

Diagram 1 Typical Wiring with VPS 504 Test on Start-up

• CAUTION : Frequency converters with insufficient shielding can cause faults in the Valve Proving Device as the result of transients. Make sure that the equipment is provided with sufficient shielding.

Black Cap

Gray Cover

Port 2

Port 1

O-ring

Test Port 3

Test Port 4

WIRING

• Do not exceed the terminal ratings given in the specifications and on the Valve Proving Device. • Remove the black cap on top of the Valve Proving Device. • Loosen the screw which secures the gray cover. • Remove the cover. • Route the wires through the conduit connector. • Connect the wiring to the appropriate screw terminals on the terminal strip. • Replace the gray cover, the screw, and the black cap. A typical wiring diagram for operating the Valve Proving Device on burner start-up only is shown in diagram 1. • A typical wiring diagram for operating the Valve Proving Device on burner start-up and shutdown is shown in diagram 2. The interface equipment (1CR, 2CR, 3CR, 1TD, 2TD), the flame safe- guard and auxiliary equipment shown in the wiring diagrams are customer supplied.

Diagram 2 Typical Wiring with VPS 504 Test on Start-up and Shut-down

 required if resetting the flame safeguard in an alarm dœs not de-energize 1CR