North American Gas Pressure Switch

Sheet 1597A-4

High/low gas pressure switch (SPDT) with automatic reset and with visual indication of switch position. Mounts directly to various ports on the Double Shutoff Valves and/or the Gas Pressure Regulators. SPECIFICATIONS Gases natural gas, propane, non-corrosive gases, and air Switch SPDT Switch Action high/low limit, NC breaks on rise, automatic reset Contact Rating UL, FM: 10 A res., 8 FLA, 48 LRA at 120 V ac CSA: 3 A res., 4.5 FLA at 300 V ac Set Point Range R830-5574: 12" - 60"w.c. R830-5576: 40" - 200"w.c.

Location The gas pressure switch can be mounted directly to the Double Shutoff Valve ports 1, 4, and 5 and/or the Gas Regulator ports A, B, and C. The pressure switch should be mounted in locations meeting the requirements of the applicable code. • Never perform work if gas pressure or power is applied, or in the presence of an open flame. • Protect surfaces. Make sure that seals and O-rings are clean and in good condition. • Once installed, perform a complete checkout including a gas leak test. • Label all wires prior to disconnection when servicing switches. Wiring errors can cause improper and dangerous operation. • Verify proper operation after servicing.

Enclosure

DMV

2 3

1

NEMA 4 Ambient/Fluid Temperature –40°F to 140°F Max. Operating Pressure 7 psi Materials in Contact w/ Gas housing:

4

5

4

5

2 3

4

1

5

1

V1

V2

2 3

1

FRI

A

C

B

B

C

cast aluminum rubber components: NBR-based rubber Approvals

B

C

UL Listed: File No. MH 16628, Guide No. MFHX FM Approved: Report J.I. 1T7A8.AF and J.I. 1Y9A9.AF CSA Certified: LR 73925

A

A

A

Port Locations

Mounting • The gas supply must be shut off and the Double Shutoff Valve must be de-energized before mounting the gas pressure switch. • Disconnect all power to the pressure switch before beginning to prevent electrical shock and equipment damage. Recommended Mounting Procedure • Remove the clear cover of the switch. • Open the plastic bag containing the mounting kit which is placed under the cover. • Take out the M4 x 20 mm self tapping socket head screws. • Use the screws to cut the threads in the predrilled holes in the flange or the side of the valve body at the desired mounting position. • Use a 3 mm hex key wrench to turn the screws. After cutting the threads remove the M4 x 20 mm socket head screws. • Fit the 10.5  2.25 mm O-ring into the groove on the back of the pressure switch.

NOTE: For stand-alone switches and other ranges, see Sheet 8757-4.

INSTALLATION • Read these instructions carefully. • Failure to follow them and/or improper installation may cause explosion, property damage, and injuries. • Installation must be done with the supervision of a licensed burner technician. • The system must meet all applicable national and local code re- quirements. • Check the ratings given in the specifications and on the switch to make sure that it is suitable for your application. • These switches require a conduit seal to meet 4.1.3.2 of NFPA 86 2011.