Combustion Catalog | Fives North American

Ordering Information | Gas Shutoff Valves

Bulletin 1599 page 8

1599 -

-

-

Orientation* L = Flow right to left R = Flow left to right

Valve Size 01 = ½ " NPT** 0 = ¾ " NPT** 1 = 1" NPT 3 = 1 ½ " NPT 4 = 2" NPT 5 = 2 ½ " NPT 5F = 2 ½ " ANSI 6 = 3" NPT 6F = 3" ANSI*** 7F = 4" ANSI*** 8F = 6" ANSI***

Upstream Valve 1 = 115V VI ONLY 2 = 115V VI W/POC and AUX Switches 3 = 220V VI ONLY 4 = 220V VI W/POC and AUX Switches

Downstream Valve 0 = NO downstream valve 1 = 115V VI ONLY 2 = 115V VI W/POC and AUX Switches 3 = 220V VI ONLY 4 = 220V VI W/POC and AUX Switches

* Orientation when viewing the valve from the visual indication (VI) side. ** Available in single valve only. *** Available in double valve only.

Example: 1599-3-12-R 1 ½ " NPT double automatic reset gas shutoff valve, upstream valve with VI, downstream valve with VI POC and AUX switches, 115Vac, Nema4, UL, FM, CSA, flow left to right. 1599-4-20-L 2” NPT single automatic gas shutoff valve, VI POC and AUX switches, 115Vac, Nema4, UL, FM, CSA, flow right to left.

ACCESSORIES/SPARE PARTS

If operating temperatures lower than 5°F (-15°C) are expected the use of an actuator heater can improve the minimum allowable temperature to -20°F (-29°C). The mini ball valve paired with the hose barb can be used to leak check the valves.

Acutator Heater: R950-11260 Actuator W/POC + AUX switch: R950-11209

¼ " Mini Ball Valve: R930-4302 1⁄8 " x ¼ " Hose Barb: R210-2509

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237

Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com

Made with FlippingBook flipbook maker