Product Overview | Air Motors
Bulletin 1600-BP page 2
The 1600 Air Motor reacts rapidly to small incremental changes in the instrument air signal. 1600- -B Air Motors incorporate a volume chamber and adjustable needle valve to slow the reac- tion time of the air motor. This speed control device enables the air motor performance to be closely matched to that of the con- trol instrument, thus eliminating the "hunting effect" and undesir- able oscillations associated with poor system design. The 1600- -BP Air Motor incorporates the above, but also uses a positioner to increase the available torque. Refer to Bulletin 1600 for information on available torque, and additional data on the air motor.
R930-6022
Needle Valve Position (from closed position)
Opening Time
Closing Time
in seconds
in seconds
2 ¼ Turns 2 Turns 1 ½ Turns
31
33 45 89
42 81
1600-BK or 1600-BPK Speed Control Kits are offered for adding the speed control feature to an existing 1600 or 1600- -P Air Motor. Kits consist of:
DIMENSIONS inches
Supply air
R930-6022 ¼ adjustable needle valve
Instrument air
19 ¼
Instrument air
¼ Adjustment needle valve
1600- -B Assembly Weight : 33 lbs
1600- -BP Assembly Weight: 35 ½ lbs
1600-BK
1600-BPK
1 2-5510-1 Chamber 1 2-5511-1 Air Tube
1 2-5510-1 Chamber 1 2-5512-1 Air Tube
2 R916-4141 Elbow Fittings 1 R930-6022 ¼ " Needle Valve 2 R066-2650 Hex Head Cap Screws
2 R916-4141 Elbow Fittings 1 R930-6022 ¼ " Needle Valve 2 R066-2650 Hex Head Cap Screws
Order by specifying 1600-BK or 1600-BPK Speed Control Kit.
DIMENSIONS SHOWN ARE SUBJECT TO CHANGE. PLEASE OBTAIN CERTIFIED PRINTS FROM FIVES NORTH AMERICAN COMBUSITON, INC. IF SPACE LIMITATIONS OR OTHER CONSIDERATIONS MAKE EXACT DIMENSION(S) CRITICAL .
WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.
CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237
Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com