Instructions 1615/1199-1 Page 7

Motor Re-calibration

1. Place the MAN/AUTO switch in the AUTO position. 2. Place the OPE / MAX / MIN slide switch (shown below) in the MIN position. This will simulate a 0% position setpoint internally to the actuator.

3. Adjust the MIN potentiometer until the actuator just starts to move from the low fire position.

4. Place the OPE / MAX / MIN slide switch in the MAX position. This will simulate a 100% position set- point internally to the actuator. 5. Adjust the MAX potentiometer until the actuator just starts to move from the high fire position. 6. Repeat steps 1-4 until no more adjustments of the MIN and MAX potentiometers are required. 7. Place the OPE / MAX / MIN slide switch in the OPE position, and place the MAN/AUTO switch in the AUTO position. The actuator will now positioned based on the input signal.

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.