Combustion Catalog | Fives North American

Loop System | Light Oil Pump

Bulletin 8563/64 Page 4

To other burner zones

P

LOOP SYSTEM

Drain (tee with plug)

*

P

At high points in system install tee with plug for venting oil line.

Fill pipe

Vent

Burner control equipment (North American Packaged Oil Trains can be used here.)

Ground line

Drain (tee with plug)

* Pressure regulator may be superfluous, especially in single zone systems.

Oil storage tank

Relief Valve

Manual Shutoff Valve

Horizontal Check Valve

Automatic Shutoff Valve

Gauge

Sensitrol ™ Oil Valve

Air-Oil Ratiotrol ™

Oil Pressure Regulator

Burner

Oil Pump

Oil Strainer

RECOMMENDED SUCTION LINE SIZES (for average conditions) Pump set Pipe size 8563-1.5 1" 8563-3.5 1"

Refer to local codes for recommended installation information. Use black iron pipe for oil lines. Use an oil resistant pipe joint compound. Suction line intake should be at least 2" off bottom of tank to allow for water and sediment accumulation. In large tanks, clearance up to 6" is recommended. Suction line must be as short as possible and absolutely leak tight to prevent pulling air into oil system. Suction line should pitch toward tank. All "take offs" to oil burners should be made from the bottom of main oil line piping to prevent air bubbles from entering burners. Burner should be above oil manifold to avoid oil siphoning through burn er. WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237

Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com