North American Compact Pressure Switches Specifications

Sheet 8757-4

These pressure switches are compact, easy to use, and offer a variety of setpoints and reset options. The state of the switch is indicated via an orange indicator light. Setpoint reading and adjustment are co-located on an easy to read dial. No vent is required with these switches since they include a restricting orifice that limits the leakage in the event of a diaphragm rupture. The restricting orifice also dampens the response to small pressure spikes, which prevents nuisance switch tripping. The switches can be mounted in any orientation (vertical mounting orientation is standard). When used with combustible gases installation of a conduit plug must be used (see NFPA 86 2011 4.1.3.2).

NOTE: Do not use with 1595 Double Shutoff Valves or 1597 Fuel Trains. See Sheet 1597-4.

CAUTION: Depending on the severity of some mechanical vibration, which may cause the pressure switch to break and remake momentarily, these switches may not be good for those types of applications.

Differential

Product

Reset

Operating

pressure

Switch action

designation

connection automatic automatic automatic automatic automatic

pressure range

(deadband)

8757-GAO-A4/4/2 8757-GAO-A4/4/3 8757-GAO-A4/4/5 8757-GAO-A4/4/6 8757-GAO-A4/4/8 . 8757-GMH-A4/4/4 8757-GMH-A4/4/6 8757-GMH-A4/4/8 8757-GML-A4/4/4 8757-GML-A4/4/6 8757-GML-A4/4/8

0.16" to 1.20"w.c. 0.40" to 4.0"w.c. 2.0" to 20.0"w.c. 12.0" to 60.0"w.c. 40.0" to 200.0"w.c. 1" to 20"w.c. 12" to 60"w.c. 40" to 200"w.c. 1" to 20"w.c. 12" to 60"w.c. 40" to 200"w.c.

0.12"w.c. 0.20"w.c. 0.40"w.c. 1.2"w.c. 4.0"w.c. 0.40"w.c. 1.20"w.c. 4.0"w.c. 0.40"w.c. 1.20"w.c. 4.0"w.c.

high/low limit, NC breaks on rise high limit, NC breaks on rise low limit, NO breaks on fall

manual manual manual manual manual manual

SPECIFICATIONS

Gases:

Connections: Process:

Natural Gas, Propane, Non-Corrosive Gases

¼ " NPT

Environment:

½ " Conduit

Electrical: Test Port:

Temperature:

–40 to 140°F

Integrated Nipple

Maximum Pressure:

7 psi (Models A4/4/2,3,4,5,6) 14 psi (Models A4/4/8)

Physical Data: Footprint:

2 13⁄16 "  2 13⁄16 "  2 ¼ "

Electrical:

Weight:

0.25 lb

Contacts: Enclosure:

SPDT

NEMA 4

Approvals:

Amp Rating (resistive):

10 for 120 V ac 5 for 240 V ac

UL353, FM, CSA