Combustion Catalog | Fives North American

Static Pressure 24VDC | Pressure Switches For use with safety PLC systems

(Amps) Switch Rating 24Vdc

Pressures Range of Operating

Max Static

(Dead Band) Differential Pressure

Action Press.

Temp F Max Ambient

Switch

Designation

Service

Rise

PSI

Approvals FM, UL, CE FM, UL, CE FM, UL, CE FM, UL, CE

Enclosure

Notes

8757-J400-449-24VDC 8757-J400-451-24VDC 8757-H400-453-24VDC 8757-H400-454-24VDC 8757-DG-2I-24VDC 8757-DG-4I-24VDC 8757-DG-20I-24VDC 8757-DG-60I-24VDC 8757-DG-200I-24VDC 8757-GAO-A4/4/2 GOLD 8757-GAO-A4/4/3 GOLD 8757-GAO-A4/4/5 GOLD 8757-GAO-A4/4/6 GOLD 8757-GAO-A4/4/8 GOLD 8757-GML-A4/4/4 SILVER 8757-GML-A4/4/6 SILVER 8757-GMH-A4/4/6 SILVER 8757-GMH-A4/4/8 SILVER

Air Air Air Air

SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDT1 SPDTI

0-20" wc 0-80" wc 0-20 psi 0-30 psi

3,225 (6) 3,225 (6) 20,225 (6) 30,225 (6)

160 160 160 160 176 176 176 176 176 140 140 140 140 140 140 140 140 140

1-2" wc 1-3" wc

1

4X 4X 4X 4X

1.6 1,6 1,6 1,6 1,3 1,3 1,3 1,3 1,3

1 1 1

0.05-0.2 psi 0.05-0.3 psi 0.08-0.12" wc 0.1-0.16" wc 0.31-0.59" wc 1.17-1.95" wc 3.12-6.63" wc

Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air Gas, Air

0.2-2.4" wc 0.4-4.0" wc 1-20" wc 12-60" wc 40-200" wc 0.16-1.2"wc 0.4-4.0"wc

8.5 8.5 8.5 8.5 8.5

0.1 0.1 0.1 0.1 0.1

FM, UL FM, UL FM, UL FM, UL FM, UL

IP65 IP65 IP65 IP65 IP65

7 7 7 7

0.12"wc 0.2"wc 0.4"wc 1.2"wc 4.0"wc 0.4"wc 1.2"wc 1.2"wc 4.0"wc

20mA 20mA 20mA 20mA 20mA 20mA 20mA 20mA 20mA

FM, UL, CSA FM, UL, CSA FM, UL, CSA FM, UL, CSA FM, UL, CSA FM, UL, CSA FM, UL, CSA FM, UL, CSA FM, UL, CSA

4 4 4 4 4 4 4 4 4

1, 3 1, 3 1, 3 1, 3 1, 3

2-20"wc 12-60"wc

40-200"wc

14

1-20"wc 12-60"wc 12-60"wc

7 7 7

1, 3, 7 1, 3, 7 1, 3, 7 1, 3, 7

40-200"wc

14

CE, ANSI/ISA

4X, Cls I, II

8757-12-20I-24VDC

Gas, Air, Oil SPDT1

-20-20" wc

75, 100 (6)

203

0.5-3.5: wc

1 res, 0.5 ind

1,5,6,9

12.27.01, UL, cUL

Div. I, II

8757-D4-30I-24VDC

Gas, Air, Oil SPDT1

4.5-30" wc

40,160 (6)

150

1.5-2.5" wc

6

FM, UL, CE, CRN, CSA

4X

1,5,6,8,9

CE, ANSI/ISA

4X, Cls I, II

8757-12-50I-24VDC

Gas, Air, Oil SPDT1

2-50" wc

75, 100 (6)

203

0.5-5" wc

1 res, 0.5 ind

1,5,6,9

12.27.01, UL, cUL

Div. I, 11

8757-D4-60I-24VDC 8757-D4-100I-24VDC 8757-D4-150I-24VDC

Gas, Air Oil SPDT1 Gas, Air, Oil SPDT1 Gas, Air, Oil SPDT1

9-60" wc 15-100" wc 22.5-150" wc

40,160 (6) 40,160 (6) 40,160 (6)

150 150 150

1.5-3.5" wc 2.5-5.5" wc 4.5-8.5" wc

6 6 6

FM, UL, CE, CRN, CSA FM, UL, CE, CRN, CSA FM, UL, CE, CRN, CSA

4X 4X 4X

1,5,6,8,9 1,5,6,8,9 1,5,6,8,9

CE, ANSI/ISA

4X, Cls I, II

8757-12-200I-24VDC

Gas, Air, Oil SPDT1

10-200" wc

75, 100 (6)

203

1-10" wc

1 res, 0.5 ind

1,5,6,9

12.27.01, UL, cUL

Div. I, II

CE,ANSI/ISA

4X, Cls I,II

8757-12-15P-24VDC

Gas, Air, Oil SPDT1

1-15 psi

300,500 (6)

203

0.5-2.0 psi

1 res, 0.5 ind

1,5,6,9

12.27.01, UL, cUL

Div. I, II

8757-B4-15P-24VDC 8757-B4-30P-24VDC

Gas, Air, Oil SPDT1 Gas, Air, Oil SPDT1

2.25-15 psi 4.5-30 psi

120,500 (6) 120,500 (6)

150 150

0.5-1.5 psi 0.5-1.5 psi

6 6

FM, UL, CE, CRN, CSA FM, UL, CE, CRN, CSA

4X 4X

1,5,6,8,9 1,5,6,8,9

CE,ANSI/ISA

4X, Cls I,II

8757-12-50P-24VDC

Gas, Air, Oil SPDT1

3-50 psi

300,500 (6)

203

0.5-4 psi

1 res, 0.5 ind

1,5,6,9

12.27.01, UL, cUL

Div. I, II

8757-B4-60P-24VDC

Gas, Air, Oil SPDT1

9-60 psi

120,500 (6)

150

1.0-3.5 psi

6

FM, UL, CE, CRN, CSA

4X

1,5,6,8,9

CE,ANSI/ISA

4X, Cls I,II

8757-12-100P-24VDC

Gas, Air, Oil SPDT1

5-100 psi

300,500 (6)

203

1.0-8 psi

1 res, 0.5 ind

1,5,6,9

12.27.01, UL, cUL

Div. I, II

8757-B4-100P-24VDC 8757-B4-200P-24VDC

Gas, Air, Oil SPDT1 Gas, Air, Oil SPDT1

15-100 psi 30-200 psi

400,1000 (6) 400,1000 (6)

150 150

1.5-5 psi 5-13 psi

6 6

FM, UL, CE, CRN, CSA FM, UL, CE, CRN, CSA

4X 4X

1,5,6,8,9 1,5,6,8,9

NOTES: 1. SPDT (Single Pole Double Throw) action means the switch makes one circuit and breaks another. 2. DPDT (Double Pole Double Throw) action means the switch makes two circuits and breaks two circuits. 3. These pressure switches must be mounted level and where they are relatively free from vibration. 4. A siphon (ordered seperately) must always be connected between the pressure switch and the line when used with steam to act as a themal buffer. Specify R830-6699 for 180° siphon, R830-6698 for a 90° siphon. 5. When used with pre-heated oil, a siphon loop must always be connected between the pressure switch and main pipe to act as a themal buffer. 6. The first pressure rating under heading "Max Static psi" is the max allowable pressure that can be applied without the need for recalibration. The second pressure rating is the proof pressure, which is defined as the max pressure to which the switch may be subjected to causing no perma- nent damage, however recalibration must be performed. 7. Manual Reset required.

8. These switches have a ¼ " vent which must be piped to an approved location. 9. These switches do not require a conduit seal to meet 4.1.3.2 of NFPA 86 2019.

Bulletin 8757 page 5