Combustion Catalog | Fives North American

Special Operating Conditions | Metering Orifice

IF LIMITED PRESSURE IS AVAILABLE If 31/2"w.c. cannot be spared for metering, larger orifice plates can be selected to take less pressure drop. (See charts on page 5 and 6).

Part of the pressure drop across an orifice may be recovered. Net recovery, in % of the drop, varies from about 15% for the small- est orifice for any pipe size to about 33% for the largest orifice .

Chart 1. Temperature Correction Factor

Chart 2. Pressure Correction Factor

1.1

2.2

1

2

0.9

1.8

0.8

1.6

0.7

1.4

0.6

1.2

0.5

1

0

200

400

600

800

1000

1200

0

5 10 15 20 25 30 35 40 45 50 Pressure, psig

Temperature, F

ALTITUDE CORRECTION FACTOR FOR AIR OR GAS

Altitude

Altitude

feet 1500 2000 2500 3000 3500 4000 4500

meters

Factor = √ G

feet

meters

Factor = √ G

457.2 609.6 762.0 914.4

0.983 0.975 0.965 0.958 0.947 0.939 0.932

5000 5500 6000 6500 7000 7500 8000

1524 1676 1829 1981 2133 2286 2438

0.921 0.913 0.905 0.898 0.886 0.878 0.870

1067 1219 1372

Bulletin 8694A Page 11

Made with FlippingBook flipbook maker