Combustion Catalog | Fives North American

Natural Gas Operation | Tempest®

All Data:............................... is based on firing with ambient combustion air.

UA-DA:................................ Published data is reasonably accurate between 6.9 and 34.6"w.c. (1.7 and 8.6 kPa) main air pressure (UA) if piped with >5 diameters of straight pipe into burner. Square rooting the UA-DA pressure drops using the published 27.7"w.c. (6.9 kPa) data is reasonably accurate between 6.9-34.6"w.c. (1.7-8.6 kPa) air pressure. Below 6.9"w.c. (1.7 kPa) the UA-DA data is suspect and should not be used for accurate air metering. Square rooting will over-estimate air flow below 6.9"w.c. (1.7 kPa) and underestimate above 34.6"w.c. (8.6 kPa). UG-DG:................................ UG-DG information can be used to approximate fuel gas flow. External gas orifices or O 2 analysis should be used for precise determination of fuel metering and air/fuel ratio.

Max % XSAir, fs Max % XSAir, UV Max % XSAir, flame rod Max % XSFuel, fs

fs - indicates the maximum flame supervisory XSAir or XSFuel using either a UV detector or the specified flame rod listed on the 4441 parts list.

Max % XSAir, ignition Max % XSFuel, ignition

ignition - indicates the maximum XSAir or XSFuel at which the integral igniter will light the burner.

DG:...................................... Tile pressures are average values and are subject to considerable variation (±10%)

NOTE: The capacity of the burners has not changed but static pressure has been transitioned to measuring static pressure in imperial units by inches of water column. Previous versions of the bulletin measured static air pressure in ounces per square inch. Conversion: 1 osi = 1.73"w.c.

NATURAL GAS OPERATION Main Air Pressure, (UA pressure tap), "w.c

4441-1

0.9

1.7

6.9

15.6

20.8

27.7

34.6

41.6

Air Flow, not burning (scfh)

1600

Air Flow, (scfh)

200

280

600

900

1025

1250

1400

1550

Air Orifice  , UA-DA, (“w.c.) Gas Orifice  , UG-DG, (“w.c.)

0.4

0.7

2.9

7.1

9.7

13.2

15.8

19.5

0.1

0.2

1

2.2

2.5

3.9

5

6

Tile Pressure, DG ("w.c.)

0.55

0.9

3.7

8.1

10.8

14.1

17.7

21

Max. % XSAir, fs, ignition

400

600

900

2000

2000

2000

2000

2000

Max. % XSFuel, fs

30 30

30 30

30 30

30 30

30 30

30 30

30 30

30 30

Max. % XSFuel, ignition

Flame Length (in.)

6

7

7

8

9

10

10

10

Flame Diameter (in.)

0.75

0.75

0.75

1

1

1

1

1

4441-2

0.3

1.7

6.9

15.6

20.8

27.7

34.6

41.6

Air Flow, not burning (scfh)

2700

Air Flow, (scfh)

200

450

1040

1650

1890

2200

2500

2700

Air Orifice  , UA-DA, (“w.c.) Gas Orifice  , UG-DG, (“w.c.)

0.15

1.23

3.7

9

11.4

16.6

20.9

25.3

0.05

0.3

1.3

3

4.4

6.7

8.5

8.6

Tile Pressure, DG ("w.c.)

0.2

0.8

2.9

5.9

7.7

9.8

12

14.3

Max. % XSAir, fs, ignition

400

1500

2000

3000

3000

3000

3000

3000

Max. % XSFuel, fs

30 30

30 30

30 30

30 30

30 30

30 30

30 30

30 30

Max. % XSFuel, ignition

Flame Length (in.)

6

8

10

10

10

10

11

10

Flame Diameter (in.)

1

2

1.5

1.5

2

2

2

2

Bulletin 4441 page 5