North American Tempest ® 4441DMC Gas Burner Instructions and Required Piping

Sheet 4441DMC-3

J Limiting Orifice Valve required within 1' of burner

L

6 Dia. min.

F ♦

F ♦

K Burner Gas Connection

E Metering Orifi ce

4 Dia. min.

H Solenoid Valve required within 3' of burner between 1807

G Ratio Regulator required within 4' of burner

I Manual Shutoff Valve

and ratio regulator

Impulse Line 3⁄8 " OD min.

C Flexible Pipe or Blower Sleeve

D Burner Air Connection

B Optional Metering Orifice

A

♦ Add unions as needed in the field for maintenance purposes.

Table 1. Component selection for Tempest ® DMC burners.

Air Side

Fuel Side

Burner Size A

B

C

D

E

F

G*

H

I

J

K

L

-3

1 ½ "

1 ½ "

1 ½ "

1 ½ "

¾"

¾"

½" / ¾" ¾" / 1" ¾" / 1" 1" / 1 ¼ "

¾"

¾"

¾"

¾"

¾"

-4-A -4-B

2" 2"

2" 2"

2" 2"

2" 2"

1" 1"

1" 1"

1" 1"

1" 1"

1" 1"

1" 1"

1" 1"

-5 -6 -7

2 ½ "

2 ½ "

2 ½ "

2 ½ "

1 ¼ " 1 ½ "

1 ¼ " 1 ½ "

1 ¼ "

1 ¼ " 1 ½ "

1 ¼ " 1 ½ "

1 ¼ " 1 ¼ " 1 ½ " 1 ½ "

3" 4"

3" 4"

3" 4"

3" 4"

1¼" / 1 ½ " 1 ½ " 1½" / 2" 2"

2"

2"

2"

2"

2"

2"

* Left side of column is recommended, right side can be used as an alternative.

Legend for Table 1

FUEL E – 8697 Metering Orifice F – Threaded Pipe Union G – 7216- - BP Regulator (with bypass) H – Solenoid Valve I – Manual Shutoff Valve J – 1807 Limiting Orifice Valve

AIR A – 1122 Manual Balancing Air Valve B – 8697 Metering Orifice (optional) C – 8770/8773 Flexible Connection or 2947 Blower Sleeve D - Burner Air Connection

K – Burner Gas Connection L – Flexible Pipe (optional)