Combustion Catalog | Fives North American

Bul 4630 page 4

IGNITION Three ignition arrangements are available: (For oven applications consult NFPA 86.) 4630-P: for direct spark ignition with provision for flame detector,

4-2408-3 Pilot and Flame rod Bracket: for 4021-15 or 4021-16 Pilot Tip plus flame rod,

4-0680-1 or 4-0680-2 Pilot Bracket: Pilot tip only (when remote flame detector isused). FEATURES If blower supplies sufficient air through burners for complete combustion, reGen ® Burners operate dependably in an inert atmosphere. Burners have machined ends, permitting assembly of various configurations without gaskets. Stainless steel flame retention strips, which give the burner its stability in high velocity air streams, are fastened so they prevent combustion between the strip and casting, resulting in lower strip and casting temperatures to prolong burner life.

Pictured from front to rear are a 4630-P Pilot Section, 4630-T Tee with 3" bottom inlet, and 4630-B 12" straight with 3" bottom inlet, all displaying various types of ignition and flame detection.

INSTALLATION

reGen Burner assemblies can be used with inspirators, but aspi- rator mixers are preferred for good turndown and air/fuel ratio control. Burners can be operated at mixture pressures from 0.35 to 12"w.c., giving 6:1 turndown. 4630 Burner sections are shipped unassembled. No gaskets are used. Be sure to order all appropriate accessories, including flanges, endplates, separator plates, and hardware kits.

When they get hot, line burner assemblies expand unevenly and tend to bow in the center. Short assemblies can be bolted down securely, and flanges will take up the expansion. For longer lengths with no bottom feed connections (or one bottom feed only at the center), support assembly rigidly at its center, leaving ends free to bow away. When two or more bot- tom feed connections are used in an assembly, install 4-3159-1 Expansion Ignition Couplings between the bottom inlets.

To order specify: 4630-(appropriate letter)-(capacity rating‡) section description, and 4630HK hardware kits to connect sections. ‡ From Table I at 4"w.c. mixture pressure (eliminate "000"). Example: 4630-T-119 Tee

replacement retention strips (with screws)

Burner section designation

flame retention strips

strip mounting screws

quantity

part no.

description

quantity/section

part no.

4630-B, -E, -H

2

4-3086-1

10

R777-0250-SX

{

{

4630-L

1 1

4-3137-1 4-3137-2

inside angle outside angle

8

R777-0250-SX

4630-N

2

4-3128-1

8

R777-0250-SX

{

{

4630-P

1 1

4-3161-1 4-3139-1 4-3139-1 4-3139-1 4-3086-1 4-3114-1 4-3114-1

on spark plug side opposite spark plug

4

R777-0250-SX

4630-S Ign. Cplg.

2 2

4 4

R777-0250-SX R777-0250-SX

{

{

1

straight

17

R777-0250-SX

4630-T

2 4

angle

4630-X

24

R777-0250-SX

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237

Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com

Made with FlippingBook flipbook maker