Instructions 4832-2 Page 4
FLAT FLAME TM BURNERS ORIFICE PLATE INSTRUCTIONS
All 4832 Burners have an orifice plate in their main air connection. Plates are mounted as shown in Figure 5 to give flame clockwise spin (viewed from rear of burner). 4832-2 thru -7
Pressure tap on main air flange must be on side opposite plate handle, as indicated by arrows. If necessary, rotate main air flange to achieve this.
Handle in this position for counterclockwise spin
Gas inlet
Gas inlet
Base of right edge of plate handle on centerline
Edge of plate handle against bolt for clockwise spin
Figure 6. Orifice Position for Dual-Fuel Conversion (See Sheet 6832-1)
Figure 5. Standard Orifice position
Flame detector
Spin can be reversed by removing two flange bolts and rotating the orifice plate 180°.
Orifice gasket (2 req'd)
Spin
For field conversion of -5 and -6 sizes from gas to dual-fuel, position orifice as shown in Figure 6. For conversion of other sizes, orifice is positioned per Figure 5. Pilot and flame detector must be installed so spin carries pilot flame toward the flame detector (Figure 7). If spin is counterclockwise, reverse pilot and flame detector positions.
Pilot
Observation Port
Orifice plate handle
Figure 7. Pilot/Flame Detector positions
4832-8-A/-8-B (Formerly 4836-8-A and -8-B)
4832-8-A orifice plate is positioned as shown at left. Posi- tion for 4832-8-B orifice plate is shown at right. Plates should not be repositioned.
WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.