Combustion Catalog | Fives North American

Instructions 4832-2 Page 4

FLAT FLAME TM BURNERS ORIFICE PLATE INSTRUCTIONS

All 4832 Burners have an orifice plate in their main air connection. Plates are mounted as shown in Figure 5 to give flame clockwise spin (viewed from rear of burner). 4832-2 thru -7

Pressure tap on main air flange must be on side opposite plate handle, as indicated by arrows. If necessary, rotate main air flange to achieve this.

Handle in this position for counterclockwise spin

Gas inlet

Gas inlet

Base of right edge of plate handle on centerline

Edge of plate handle against bolt for clockwise spin

Figure 6. Orifice Position for Dual-Fuel Conversion (See Sheet 6832-1)

Figure 5. Standard Orifice position

Flame detector

Spin can be reversed by removing two flange bolts and rotating the orifice plate 180°.

Orifice gasket (2 req'd)

Spin

For field conversion of -5 and -6 sizes from gas to dual-fuel, position orifice as shown in Figure 6. For conversion of other sizes, orifice is positioned per Figure 5. Pilot and flame detector must be installed so spin carries pilot flame toward the flame detector (Figure 7). If spin is counterclockwise, reverse pilot and flame detector positions.

Pilot

Observation Port

Orifice plate handle

Figure 7. Pilot/Flame Detector positions

4832-8-A/-8-B (Formerly 4836-8-A and -8-B)

4832-8-A orifice plate is positioned as shown at left. Posi- tion for 4832-8-B orifice plate is shown at right. Plates should not be repositioned.

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237

Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com

Made with FlippingBook flipbook maker