Combustion Catalog | Fives North American

Bulletin 8663B Page 2

8663B- Manifold

Pneumatic

Control

Reference Manifold Schematic

Logic

Valve

Designation

Description

Configuration

13-E

Both burners cycling

B,C,D, and E

MS13

Both burners in stop cycle Both burners in direct fire Either burner in direct fire with its twin in stop cycle Both burners in stop cycle Both burners in direct fire Either burner in direct fire with its twin in stop cycle Both burners cycling

13-P

A,B,C,D,E, and F

MS13

Manifold Schematic for 8663B- -E and -P

(MS12) Basic cycle control plus direct fi ring of both burners--burner 'A' fi ring, burner 'B' exhausting

(MS11) Basic cycle control-- burner 'A' fi ring, burner 'B' exhausting

A OPT. 'B'G 'B'E 'A'A 'A'G 'A'E OPT. F

Field piping by customer (typical)

Plugged

E

CACV ECV GCV 'A' GCV 'A' 'B' 'B'

'B'A 'A'E 'A'G 'A'A

GCV ECV CACV 'A' CACV 'A' 'A' 'B' 'B' 'B' GCV ECV

F

OPT.

B

C

C

Compressed air supply P

Compressed air supply

P

B

'B'A

A

OPT.

'B'E 'B'G

CACV

'B'

Muf fl er

Muf fl er

ECV 'A' Field piping by customer (typical)

Manifold port identi fi cation

Manifold port identi fi cation

LEGEND: A & F - Fuel Cycle Control Solenoid Valve B & E - Air Exhaust Cycle Control Solenoid Valve C & D - Cycle Permissive Solenoid Valve GCV - Gas Cycle Valve Actuator CACV - Combustion Air Cycle Valve Actuator ECV - Exhaust Cycle Valve Actuator Solid line indicates pressurized --------- Dashed line indicates venting 'A' & 'B' Letter in quotes indicates burner designation

(MS13) Basic cycle control plus direct fi ring either one or both burners--burner 'A' fi ring, burner 'B' exhausting

Field piping by customer (typical)

E

'A'E 'A'G 'A'A OPT.

GCV ECV 'A' CACV 'A' 'A'

F

D

Compressed air supply P

B

'B'A

Indicates energized solenoid valve Indicates de-energized solenoid valve Indicates piping connection

CACV GCV ECV

'B' 'B' 'B'

A

'B'E 'B'G OPT.

C

Muf fl er

OPT - Optional

Manifold port identi fi cation

For Dimensions, see Dimensions 8663B For Trouble-Shooting, see Trouble-Shooting 8663B For Installation, Operation, and Maintenance Instructions, see Installation 8663B For Recommended Spare Parts, see Spare Parts 8663B

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237

Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com