Combustion Catalog | Fives North American

Supplement 6100-1 Page 2

CAPACITIES  

CHARACTERISTICS

BLOWER

Table 1.

Main air,

Natural

Oil,

Flame Size,

dia.  length

gph  

hp

rpm

Burner Data

Btu/hr

scfh

gas, scfh  

2.5'  5' 2.5'  5' 2.5'  5' 2.5'  5'

4131A 5131A- 6131A-

4 200 000 4 200 000 4 200 000 4 200 000 6 300 000 6 300 000 6 300 000 6 300 000

50 000 50 000 50 000 50 000 76 000 76 000 76 000 76 000

4 200

1.5 1.5 1.5 1.5

3450 3450 3450 3450 3450 3450 3450 3450 1750 1750 3450 3450 3450 3450 3450 3450 1750 1750 1750 1750 1750 1750 1750 3450 3450 3450 3450

[

2

30.3 27.9 27.9

5,6

4 200 4 200

CR

 7'  7'  7'  7'

4131B 5131B- 6131B-

6 300

3' 3' 3' 3'

3 3 3 3 5 5 5 5 5

[ [

2

50.7 42.0 42.0

5,6

6 300 6 300

CR

3.5'  11' 3.5'  11' 3.5'  12' 3.5'  12' 3.5'  12' 3.5'  12' 3.5'  12' 3.5'  12'

5131CL- 6131CL- 4131C 5131C- 6131C-

4

10 500 000 126 000 10 500 000 126 000 12 300 000 141 000 12 300 000 141 000 8 400 000 105 000 8 400 000 105 000 8 400 000 105 000 8 400 000 105 000 18 000 000 216 000 18 000 000 216 000 16 800 000 200 000 25 200 000 300 000 25 200 000 300 000 25 200 000 300 000 25 200 000 300 000 30 000 000 360 000 30 000 000 360 000 30 000 000 360 000 30 000 000 360 000

78 70

5,6

10 500

[ [ [ [

12 300

 

2  

91

5,6

8 400

55.8

8 400

7.5 7.5 7.5 7.5 7.5 7.5

4131CS    

2   2  

55.8 55.8

5131CS- 6131CS- 4131D 5131D- 6131D-

8 400

 12'  12'  12'  12'  12'  12'  12'  18'  18'  18'  18'

18 000

4' 4' 4' 4' 4' 4' 4' 4' 4' 4' 4'

2

131 112

5,6

16 800

4131E 5131E- 6131E-

25 200

10 10 10 10

2

182 167 167

5,6

25 200 25 200

CR

4131FA

30 000

20 20 20 20

[

5131FA - 6131FA-

2

222 200 200

5,6

30 000 30 000

CR

 Burner model number breakdown is as follows: First digit identifies burner as— 4 = gas only 5 = oil only 6 = dual-fuel Next 3 digits, 131, identify burner as part of integral fan series Letters designate burner frame size Numerals or CR after hyphen show fuel selection— 2 = #2 or #4 oil 5 = #5 oil 6 = #6 CR = crude oil

 Capacities and flame lengths are with 20% excess air and1.5"wc backpressure in a cold, tight chamber. Excess air operation at rates greater than 20%, through reduction of fuel input, is possible for nearly all of these burners. Consult factory for maximum excess air rate for any particular size and fuel.  Fuel rates are based on the following calorific values: 1 000 Btu/cu ft of natural gas

135 000 Btu/gallon of light (#2 or #4) oil 150 000 Btu/gallon of heavy (#5 or #6) oil 145 000 Btu/gallon of crude oil

 Capacity is with 15% excess air and 0.5"wc backpressure.  Capacity is with 20% excess air and 5"wc backpressure.