Combustion Catalog | Fives North American

Dimensions | Dual-Fuel ™ Burners

DIMENSIONS inches

¾ NPT for flame detector and Observation Port  (45° to mtg. plate)

3 19⁄32 rad.

E

Recommended Sensitrol™ Oil Valve 

6425 cylindrical hole T –dia.

¾ NPT for Pilot Tip  (45° to mtg. plate)

¾ wide slotted holes on cast mtg. plates

P

45°

6425- -MB Milk Bottle shaped hole U –dia.

Q

H

1 1⁄8

G

D  sq.

45°

P

F

C –NPT Atomizing Air

B –NPT Gas

3⁄8 NPT Oil 

8– 3⁄8 bolts on 7 ½ BC (-2 thru -6) 8– ½ bolts on 9 3⁄8 BC (-7-A thru -8-A)

1⁄8 press. tap

A –NPT Main Air

J

P

P

K

9" long for 6425 13 ½ " longfor 6425- -MB

2 9⁄16

R

R

L

S sq.

M 

N 

NOTE : For 6425-8-A, the air and gas connections cannot be piped in the same plane, as shown on other side, because the "flower pot" type air connection flange would interfere with the 2 ½ " gas line.

DIMENSIONS SHOWN ARE SUBJECT TO CHANGE. PLEASE OBTAIN CERTIFIED PRINTS FROM FIVES NORTH AMERICAN COMBUSTION, INC. IF SPACE LIMITATIONS OR OTHER CONSIDERATIONS MAKE EXACT DIMENSION(S) CRITICAL .

Burner designation

D 

M 

N  18 3⁄8 18 3⁄8 18 3⁄8 18 3⁄8 18 3⁄8 22 5⁄8 22 5⁄8 22 5⁄8

A

B

C

E

F

G

H

J

K

L

6425-2 6425-3 6425-4 6425-5 6425-6

1 ¼ 1 ½

1 1

8 ½ 8 ½ 8 ½ 8 ½ 8 ½

5 ¼ 5 ¼ 5 ¼ 5 ¼

2 2 2 2 2

1 3⁄8 1 3⁄8 1 3⁄8 1 3⁄8 1 3⁄8 2 1⁄8 2 1⁄8 1 ¾

4 3⁄8 4 3⁄8 4 3⁄8 4 3⁄8 4 3⁄8 5 7⁄8 5 7⁄8 5 7⁄8

8 3⁄8 8 3⁄8 8 3⁄8 8 3⁄8 8 3⁄8

11 5⁄16 11 5⁄16 11 5⁄16 11 5⁄16 11 5⁄16 15 1⁄8 15 1⁄8 15 1⁄8

15 13⁄16 15 13⁄16 15 13⁄16 15 13⁄16 15 13⁄16 20 1⁄16 20 1⁄16 20 1⁄16

¾ ¾ ¾

½ ½ ½ ½ ½

2

1 ¼ 1 ½ 1 ½ 2 ½ 2 ½ 2 ½

2 ½

1 1

3 4 4 6

5 9⁄16 6 15⁄16 6 15⁄16

6425-7-A 6425-7-B 6425-8-A

1 ¼ 1 ¼

10 10 10

2 5⁄8 2 5⁄8 2 5⁄8

11 11 11

9⁄16 9⁄16 9⁄16

2

10 11⁄16

approx. flame lengths * with 16 osi Main Air (in open furnace)

Recommended

Sensitrol ™ Oil Valve 1813-02-A 1813-02-A 1813-02-A 1813-02-A 1813-02-B 1813-02-C 1813-02-C 1813-02-D

Burner

wt,

designation

P

Q

R

S

T 5 5 5 5 5 7 7 7

U 3 3 3 3 3

in lb

gas

oil

6425-2 6425-3 6425-4 6425-5 6425-6

5 ¼ 5 ¼ 5 ¼ 5 ¼ 5 ¼ 6 1⁄8 6 1⁄8 6 1⁄8

10 ½ 10 ½ 10 ½ 10 ½ 10 ½ 12 ¼ 12 ¼ 12 ¼

6 6 6 6 6

12 12 12 12 12

83 83 83 83 83

½ '

1 ½ '

1 ½ '

2'

2'

2 ½ '

2 ½ '

3' 4' 6' 6' 7'

3' 5' 6' 7'

6425-7-A 6425-7-B 6425-8-A

6 ¾ 6 ¾ 6 ¾

13 ½ 13 ½ 13 ½

4 ½ 4 ½

139 139 145

All burners use 4011-11 or 4011-12 Pilot Tips. 6425- -MB Burners have a 1⁄16 " gasket between mounting plate and burner body.  Pilot, flame detector, and Observation Port positions are interchangeable as long as Pilot and flame detector are in adjacent holes.   Opening in furnace shell should be about ½ " larger than dimension D to allow for fillets and draft on mounting plate.  ¼ " air pressure tap on -2, -3, -4, -5 and -6.   Dimensions M and N assume use of a 3⁄8 " close nipple (not furnished by North American) between burner and Sensitrol TM Valve.  Metal tubing is available as an extra cost option (order as PN 3-0310-7).  Optional (recommended) Sensitrol Oil Valve is not included as part of the burner assembly, and must be ordered separately.

* 6425 Burners with standard tiles

Tiles for 6425 Burners

Standard

Milk Bottle

Burner

70% alumina 80% alumina

designation

PN

PN

6425-2 thru -6 6425-7A, -7B, -8A

4-2121-2 4-2142-2

OC4-2332-1 OC4-2547-2

All tiles end use limit temperature is 3200°F.

Bulletin 6425 Page 3

Made with FlippingBook flipbook maker