Sheet 6435-3 Page 6

6435-6 – 800°F Main Air, Cold Atomizing Air

Main Air Pressure, osi

Burning Natural Gas

0.1

1

4

9

16

20

Main air, scfh, stoich.

1200 2600 5200 7900 10 700 12 400

Atom. air, scfh at 20 osi, stoich. †Total air, scfh, stoich. Gas flow, stoich., scfh Gas pressure, stoich., osi Flame length, in., stoich. Flame diameter, in., stoich. Tile pressure, osi, stoich.

410

410

400

400

400

380

1750 3150

5750 8450 11 200 12 900

175 0.1

315 0.6

575

845

1 120 1 300

2.2 24

4.6

7.8 24

9.5

15

21

24

24

4 0

4

5

6

6

7

0.3

1.0

2.0

3.7

4.2

Max. %XSAir

‡Flame supervision

25

200 300 250

400 750 500

500 750 500

550 750 400

650 650 250

‡Stability

125 100

‡Ignition--pilot

Max. %XSFuel

30

30

30

30

30

30

Burning #2 Oil

0.1

1

4

9

16

20

Main air, scfh, stoich.

1400 2650 5350 8100 10 800 12 400

Atom. air, scfh at 30 osi, stoich.

510

510

500

500

510

460

†Total air, scfh, stoich. Oil flow, stoich., gph

2050 3300 6000 8750 11 500 13 000

1.5 1.4

2.4

4.3

6.3 1.8

8.2 2.0

9.3

Oil pressure, stoich., psi Flame length, in., stoich. Flame diameter, in., stoich. Tile pressure, osi, stoich

1.5 24

1.7 24

2.1 24

12

24

24

6

7

8

8

8

9

0.04

0.15

0.9

1.9

3.4

4.4

Max. %XSAir

‡Flame supervision

25 50 25 30

125

250 400 250

400 600 400

675 700 675

500 800 500

†Stability

200

†Ignition--pilot

125

Max. %XSFuel

30

30

20

20

20

The external metal temperatures recorded with neutral furnace pressure and in a cold chamber with preheated air were as follows:

Metal temperature, F

Body

Preheat Air

Body

(Main Air

temperature, F (near flange)

Inlet Flange)

400 600 800

410 560 720

310 440 570

† Total air is main air plus atomizing air plus 140 scfh for pilot air. ‡ Honeywell Ultravision Flame Detector C7027A and Honeywell Flame Supervision Protectorelay RA890G yielded 1.5 micro amps or greater for all above rates. WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.