Combustion Catalog | Fives North American

Product Overview | 6514 Fire•All ™

Flame Supervision. An ultraviolet cell‡ will monitor pilot or main flame on gas or oil. For maximum safety, North American urges interrupted pilots when flame safeguards are used--pilots should be on only for a preset ignition period (usually 15 seconds), after which flame supervision detects main fire only. Adapters for mounting flame detection devices on 6514 Burners are tabulated on Bulletin 8832. Tile/Installation. Burner tiles are cast refractory rated for 2800°F furnace temperature. They should be supported securely in the furnace wall by castable refractory (not insulation) at least 9" thick all around the tile, extending back to the furnace shell and securely anchored to it. (See Supplement DF-M1.) Tiles are replaceable in the field except for the 6514-10, whose mounting must be returned to the factory for tile replacement (or purchase a spare mounting plate with a tile cast onto it). Complete burners include tile, mounting plate, and an observa- tion port into which a small quantity of atomizing air is intro- duced to keep the glass clear. Order pilot tips and Sensitrol™ Oil Valve separately. See 6514 Dimension Sheet for recommended Sensitrol™ oil valve and premix pilot tip. Jacketed Tile options are available for applications where the tile is not supported by furnace refractory. Jackets are available in three different metals and have maximum temperature ratings for each. They must be protected with sufficient insulation so as not to exceed rated temperature.The maximum temperature rating depends upon frequency of heat-up/cool-down cycles. As an example, batch annealing furnaces that are heated and cooled every day should use the "intermittent exposure" ratings. Continuous annealing furnaces that remain at the same temperature for months at a time, can use the higher "continuous" rating.

Burner Nose options are available for sizes shown below and can be specified in the product number. The burner nose establishes main combustion air flow and influences flame propagation. Nose material is either cast iron that is suitable for cold air applications up to 1800°F, or cast stainless alloy for preheated air (maximum 700°F) applications up to 2400°F.

Mat'l

Cap'y -6

-7 -8A -8B -9 -10

Cast iron 1.0 Cast Alloy 1.0

√ √

√ √ √ √

√ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √

Cast iron

1.1

Cast Alloy 1.1 Cast iron 1.2 Cast Alloy 1.2 Cast iron 1.3 Cast Alloy 1.3

The product designation 1.0 represents standard main air capacity shown on page 1. Use of an extra capacity burner nose will result in either more air at 16 osi or standard air flow at lower pressure. Extending the capacity of the burner by increasing air pressure beyond 16 osi, or using the extra capacity nose, is acceptable for most gas and light oil applications. Specific applications involving either low Btu fuels or heavy oil and extra capacity should be reviewed with North American. Also, when firing extra capacity, the combustion air flow velocity within the supply piping, and associated pressure loss, can be excessive for some burners.The -8B, -9 and -10 products when operated at 1.2 or 1.3 capacity will develop high pipe velocity based on the burner’s air connection size. As an alternative to increasing blower pressure, an oversized air inlet can be purchased separately for these size burners. The connections are SW-type (slip-on sleeve or welded construction) and are one pipe size larger than the standard supply. Nose and oversize air connection part numbers can be found in supplement literature (see Parts List and Burner Options documents). Options are available for the 6514 burner but require consultation with North American sales for application and ordering information. See Sheet 6514-3 for an overview of burner options.

Continuous Intermittent max.temp. exposure

Designation Jacket Metal

6514- -LC 6514- -L4 6514- -L9

carbon steel 304 stainless 309 stainless

700°F 1600°F 1900°F

700°F 1500°F 1800°F

‡ Cleaning air must be introduced into the port downstream of the sensor to keep oil and poc's off the lens.

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

Bulletin 6514 Page 3