Combustion Catalog | Fives North American

6435-5 with Cold Main Air, Cold Atomizing Air

Main Air Pressure osi/"w.c./mbar

Not Burning Main Air Flow scfh (Nm 3 /h)

12 100 (323)

Atom. air, scfh (Nm 3 /h) @ 30 osi/51.9"w.c./129 mbar Atom. air, scfh (Nm 3 /h) @ 8 osi/13.8"w.c./34.5 mbar

700 (18.7) 520 (13.9)

Burning Natural Gas

osi

0.2 0.3 0.9 895

1

4

9

16

"w.c. mbar

1.7

6.9 17.2

15.6

27.7

4.3

39

69

Main Air Flow, stoich. ratio

scfh

2060 (55.1)

4460

6950 (189)

9500 (254)

(Nm 3 /h)

(23.9)

(119) 485

Atom. Air Flow @ 8 osi/35.5 mbar stoich. ratio

scfh

520

510

450

400

(Nm 3 /h)

(13.9) 1600 (42.8)

(13.6) 2760 (73.8)

(13.0) 5150 (138)

(12.0) 7600 (203)

(10.7)

† Total Air Flow, stoich, ratio

scfh

10 100 (270) 1010 (27.0)

(Nm 3 /h)

Gas Flow stoich. ratio

scfh

160

276

415

760

(Nm 3 /h)

(4.28)

(7.38)

(13.8)

(20.3)

Gas pressure stoich. ratio Tile pressure stoich. ratio

"w.c. (mbar) "w.c. (mbar)

0.17 (0.4) 0.17 (0.4)

1.4 (3.4) 0.7 (1.7)

4.85 (12.1) 2.4 (6.0)

10.9 (27.1) 18.7 (46.5)

6.1 (15.1)

10.0 (25.0)

‡ Max. % XSAir Stablility UV Flame supervision

20 20 20 30

250 250

400 400

350 325

350 200 100

Max. % XSAir Ignition--pilot

Max. % XSAir Ignition--direct spark

65 30

60 30

75 30

Max. % XSFuel

10

Flame length stoich. ratio Flame diameter stoich. ratio

inch (mm) inch (mm)

12 (305) 4.0 (76)

18 (457) 4.0 (76)

19 (483) 5.0 (127)

19 (483) 6.0 (152)

19 (483) 6.0 (152)

Burning #2 Oil

Main Air Flow, stoich. ratio

scfh

895

2110

4760 (127)

7450 (199) 640 (17.1) 8280

10 000

(Nm 3 /h)

(23.9)

(56.4)

(267)

§ Atom. Air Flow @ 30 osi/129 mbar stoich. ratio

scfh

695

690

670

585

(Nm 3 /h)

(18.6) 1780 (47.6)

(18.4) 2990 (79.9)

(17.9) 5620 (150)

(15.6)

† Total Air Flow, stoich, ratio

scfh

10 775

(Nm 3 /h)

(221)

(288)

Oil Flow stoich. ratio

gph (lph)

1.1

2.0

3.9

5.8

7.6

(4.16)

(7.57)

(14.8)

(22.0)

(28.8)

Oil pressure stoich. ratio Tile pressure stoich. ratio

psi (mbar) "w.c. (mbar)

1.0 (69)

1.2 (83) 0.9 (2.2)

1.4 (97) 2.2 (5.6)

1.6 (110) 4.8 (12.1)

1.8 (124)

0.14 (0.3)

9.0 (22.4)

‡ Max. % XSAir Stability UV Flame supervision

25 25

125 125 20+

275 275

300 225

350 150

Max. % XSAir. Ignition--pilot

Max. % XSFuel

20+

20

20

20

Flame Length stoich. ratio Flame diameter stoich. ratio

inch (mm) inch (mm)

10 (254) 3.0 (76)

14 (356) 4.0 (76)

24 (610) 5.0 (127)

24 (610) 6.0 (152)

24 (610) 6.0 (152)

† Total air is main air plus atomizing air plus 190 scfh for pilot air. ‡ Honeywell Ultravision Flame Detector C7027A and Honeywell Flame Supervision ProtectoRelay RA890G yielded 1.5 micro amps or greater for all above rates. § 30 osi is recommended atomizing air pressure for oil, but all burners will operate on oil with 22 osi atomizing air (at the burner) and 10% or more excess air.

■ Electrode setup used was that shown in drawing B4-7249. The cooling air was le on for ignition tests. • Direct spark ignition on oil is not considered a viable lighting method due to the lack of repeatability.

▲ Figure includes 110 scfh air for cooling on spark for #2 oil.  Figure includes 75 scfh air for cooling on spark for natural gas. Velocity: The distance (in inches) from the tile outlet to the point where the tile velocity pressure is 0.1"w.c. (1259 fpm) is 130" on gas and 130" on oil (firing stoichiometric with 16 osi main air pressure). Bulletin 6435 Page 13