Combustion Catalog | Fives North American

6435-2 | 800 °F Main Air, Cold Atomizing Air

Main Air Pressure osi/"w.c./mbar

Burning Natural Gas

osi

0.2 0.3 0.9 200

1

4

9

16

26

"w.c. mbar

1.7

6.9 17.2 950

15.6

27.7

45.0

4.3 510

39

69

112

Main Air Flow, stoich. ratio

scfh

1380 (36.9)

1860 (49.7)

2360 (63.1)

(Nm 3 /h)

(5.35)

(13.6)

(25.4)

Atom. Air Flow @ 8 osi/35.5 mbar stoich. ratio

scfh

60

60

60

50

40

20

(Nm 3 /h)

(1.60)

(1.60)

(1.60)

(1.34) 1560 (41.7)

(1.07) 2030 (54.3)

(0.53) 2510 (67.1)

† Total Air Flow, stoich, ratio

scfh

390

700

1140

(Nm 3 /h)

(10.4)

(18.7)

(30.5)

Gas Flow stoich. ratio

scfh

39

70

114

156

203

251

(Nm 3 /h)

(1.04)

(1.87)

(3.05)

(4.17)

(5.43)

(6.71)

Gas pressure stoich. ratio Tile pressure stoich. ratio

"w.c. (mbar) "w.c. (mbar)

0.35 (0.9) 0.17 (xx)

1.0 (2.6) 0.9 (2.2)

2.8 (6.9) 5.2 (12.9) 8.7 (21.5)

13.3 (33.2) 11.2 (28.0)

2.2 (5.6) 4.3 (10.8)

7.1 (17.7)

‡ Max. % XSAir Stablility UV Flame supervision

400 400

400 400

400 400

400 400

400 400

400 400

Max. % XSAir Ignition--pilot

Max. % XSFuel

30

30

30

30

30

30

Flame length stoich. ratio Flame diameter stoich. ratio

inch (mm) inch (mm)

6 (152) 1.5 (38)

8 (203) 2.0 (51)

10 (254) 2.0 (51)

11 (279) 2.5 (64)

12 (305) 2.5 (64)

14 (356) 2.5 (64)

Burning #2 Oil

Main Air Flow, stoich. ratio

scfh

220

430 (11.5)

900

1390 (37.2)

1850 (49.5)

2320 (62.0)

(Nm 3 /h)

(5.88)

(24.1)

Atom. Air Flow @ 30 osi/129 mbar stoich. ratio

scfh

170

180

200

210

220

220

(Nm 3 /h)

(4.54)

(4.81)

(5.35) 1230 (32.9)

(5.61) 1730 (46.2)

(5.88) 2200 (58.8)

(5.88) 2670 (71.4)

† Total Air Flow, stoich, ratio

scfh

520

740

(Nm 3 /h)

(13.9) 0.38

(19.8) 0.53 (2.01)

Oil Flow stoich. ratio

gph (lph)

0.88

1.24

1.57

1.90

(1.44)

(3.33)

(4.69)

(5.94)

(7.19)

Oil pressure stoich. ratio Tile pressure stoich. ratio

psi (mbar) "w.c. (mbar)

0.1 (6.9) 0.5 (34.5) 0.7 (48.3)

1.0 (69) 1.7 (4.3)

0 (0)

0 (0)

0.17 (0.4) 0.9 (2.2)

1.2 (3.0)

‡ Max. % XSAir Stability UV Flame supervision

50 50 25

50 50 25

175 175

250 250

400 400

400 400

Max.% XSAir gnition--pilot

Max. % XSFuel

25

25

20

5

Flame Length stoich. ratio Flame diameter stoich. ratio

inch (mm) inch (mm)

4 (102) 2.0 (51)

8 (203) 2.0 (51)

10 (254) 2.0 (51)

11 (279) 2.5 (64)

12 (305) 2.5 (64)

12 (305) 2.5 (64)

The external metal temperatures recorded with neutral furnace pressure and in cold chamber with preheated air were as follows:

Metal temperature °F (°C)

Preheat Air

Body

Body

Backplate

temperature, °F (°C)

(near flange) (main air inlet flange )

400 (204) 600 (316) 800 (427)

240 (116) 290 (143) 305 (152)

260 (127) 330 (166) 470 (243)

240 (116) 350 (177) 450 (232)

† Total air is main air plus atomizing air plus 130 scfh for pilot air. ‡ Honeywell Ultravision Flame Detector C7027A and Honeywell Flame Supervision ProtectoRelay RA890G yielded 1.5 micro amps or greater for all above rates.

Bulletin 6435 Page 16

Made with FlippingBook flipbook maker