Combustion Catalog | Fives North American

6435-5 | 800 °F Main Air, Cold Atomizing Air

Main Air Pressure osi/"w.c./mbar

Burning Natural Gas

osi

0.2 0.3 0.9 790

1

4

9

16

"w.c. mbar

1.7

6.9 17.2

15.6

27.7

4.3

39

69

Main Air Flow, stoich. ratio

scfh

1580 (42.2)

3270 (87.4)

5050 (135)

7200 (192)

(Nm 3 /h)

(21.1) 480 (12.8) 1460 (39.0)

Atom. Air Flow @ 8 osi/35.5 mbar stoich. ratio

scfh

460

430 (11.5)

410

380

(Nm 3 /h)

(12.3) 2230 (59.6)

(11.0) 5650 (151) 565 (15.1)

(10.2) 7770 (208)

† Total Air Flow, stoich, ratio

scfh

3890 (104)

(Nm 3 /h)

Gas Flow stoich. ratio

scfh

146

223

389

777

(Nm 3 /h)

(3.90)

(5.96)

(10.4)

(20.8)

Gas pressure stoich. ratio Tile pressure stoich. ratio

"w.c. (mbar) "w.c. (mbar)

0.26 (0.6)

1.4 (3.4) 0.6 (1.5)

4.3 (10.8)

9.2 (23) 4.0 (9.9)

15.9 (40) 6.7 (16.8)

— 75 75

1.9 (4.7)

‡ Max. % XSAir Stablility UV Flame supervision

200 200

400 400

400 400

350 350

Max. % XSAir Ignition--pilot

Max. % XSAir Ignition--direct spark

5 XSF

30 XSF

50

40

50

Max. % XSFuel

30+

30+

30+

30+

30+

Flame length stoich. ratio Flame diameter stoich. ratio

inch (mm) inch (mm)

12 (305) 4.0 (102)

19 (483) 5.0 (127)

19 (483) 5.0 (127)

19 (483) 5.0 (127)

22 (559) 5.0 (127)

Burning #2 Oil

Main Air Flow, stoich. ratio

scfh

790 (21.1) 660

1710

3580 (95.7)

5280

7300 (195)

(Nm 3 /h)

(45.7)

(141) 580

Atom. Air Flow @ 30 osi/129 mbar stoich. ratio

scfh

620

600

560

(Nm 3 /h)

(17.6) 1640 (43.8)

(16.6) 2520 (67.4)

(16.0) 4370

(15.5) 6050 (162)

(15.0) 8050

† Total Air Flow, stoich, ratio

scfh

(Nm 3 /h)

(117)

(215)

Oil Flow stoich. ratio

gph (lph)

1.1

2.0

3.9

5.8

7.6

(4.2)

(7.6)

(14.8)

(22.0)

(28.8)

Oil pressure stoich. ratio Tile pressure stoich. ratio

psi (mbar) "w.c. (mbar)

1.05 (72)

1.1 (76) 0.5 (1.3)

1.25 (86) 1.6 (4.1)

1.35 (93) 3.4 (8.4)

1.5 (103) 5.9 (14.7)

— 30 30

‡ Max. % XSAir Stability UV Flame supervision

125 125 20+

275 275 20+

300 300 20+

350 350

Max.% XSAir gnition--pilot

Max. % XSFuel

20+

20

Flame Length stoich. ratio Flame diameter stoich. ratio

inch (mm) inch (mm)

10 (254) 3.0 (76)

11 (279) 4.0 (102)

19 (483) 5.0 (127)

21 (533) 5.0 (127)

22 (559) 5.5 (140)

† Total air is main air plus atomizing air plus 130 scfh for pilot air. ‡ Honeywell Ultravision Flame Detector C7027A and Honeywell Flame Supervision ProtectoRelay RA890G yielded 1.5 micro amps or greater for all above rates. • The electrode setup used was that shown in drawing B4-7249. The cooling air was shut off for ignition and turned back on aerwards.

Maximum body temperature 550 °F

Bulletin 6435 Page 19

Made with FlippingBook flipbook maker