Combustion Catalog | Fives North American

Sheet 4014 Page 5

NORTH AMERICAN PILOT ACCESSORIES

1400 (1486A-02B) Solenoid Valves, Specs, Dimensions 1821B Shutoff Valves 1122 Manual Butterfly Valves for Gas and Air

4065 Ignition Transformers 4074 Push Button Ignition Station 4085 Ignition Cable

Accessories (order separately)

Part Name

4014-1-T

4014-2-T

4014-3-AT

4014-3-BT

4014-4-T

Pilot Regulator

7218-01 1122-1 8777-1

7218-01 1122-2 8777-2

7218-0 1122-3 8777-3

7218-1 1122-4 8777-4

7218-1 1122-4 8777-4

Air Butterfly Valve Air Flex Connector

Boost Gas Flex Connector Main Gas Flex Connector

8773-01-TT/9 8773-01-TT/9

8773-01-TT/9 8773-01-TT/9

8773-01TT/9 8773-0-TT/9

8773-01-TT/9 8773-1-TT/9

8773-01-TT/9 8773-1-TT/9

Main Gas Manual Shutoff Valve Main Gas Manual Shutoff Valve

1821B-01

1821B-0

1821B-1

1821B-1

1821B-1

1821B-01-LH

1821B-0-LH

1821B-1-LH

1821B-1-LH

1821B-1-LH

(with Locking Handle)

See Bulletin 8666 for more detailed information 8666 Testips

Allow 6" minimum flame clearance

The 8666 Testip facilitates setting air/fuel ratio when premix flames are not easily visible. The Testip is installed in a positive pressure mixture line and lit with a manual torch. Air/gas ratio is adjusted in the mixer until Testip flame looks appropriate. Use caution with 8666 Testips they are small burners and get very hot when run. Outdoors, the flame can be difficult to see in direct sunlight. Testips will not work in systems that operate with negative mixture pressure.

1⁄8 NPT

5⁄8

4 11⁄16 "

- A purple tinge indicates a lean ratio. - A greenish-blue inner cone denotes a rich fire. - Compare Testip flame with known correct burner ratio setting.

4055-X-ERA

Explosion Resistant Assembly (ERA) Igniters See Bulletin 4055 for more detailed information

4"

The 4055-X-ERA 10mm igniter is intended to ignite pilot tips in Class 1 Div. 2 applications. It has a ¾ "-20 threaded igniter connection for sealed aircraft type ignition wiring (see Sheet 4085). Although the wiring method used between the ignition transformer and the spark plug was designed and chosen to be suitable for use in Class 1 Div. 2 hazardous locations, it DOES NOT carry certifications or third party approvals.

1 ½ "

M10X1

¾ -20 UNEF 2A For use with 4085-ERA cable

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237

Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com

Made with FlippingBook flipbook maker