Combustion Catalog | Fives North American

Capacity, Dimensions | 6795 Magna-Flame ™

COMBUSTION AIR CAPACITY, (scfh) for Btu/hr, multiply by 100

FLOW RATE of ATOMIZING MEDIUM for sizing piping only "Maximum"  steam flow, lb/hr compr. air, scfm with 80 psi steam with 80 psi air "Maximum" 

FLAME DIMENSIONS @ 8 osi main air and 10% XSair. add 10% for heavy oil

Air pressure drop across burner, osi

Burner Designation 6795-10-43 6795-12-43 6795-14-43 6795-16-43 6795-18-43 6795-20-43

8.0 

1.0

5.0

6.0

Length Diameter

47 500 106 000 116 000 70 000 157 000 172 000

134 000 198 000

140 225 225 660 660 660

52 83 83

11'

4' 5' 5' 5' 6' 6'

15'

95 500 214 000 234 000 270 000 121 000 269 000 295 000 340 000 155 000 346 000 380 000 438 000 200 000 447 000 490 000 565 000

20' 25' 30' 35'

244 244 244

 Because of a positive pressure in the burner, it is difficult to light with a torch unless the air is turned very low and a strong pressure torch is used.  Maximum recommended pressure  See explanation in the text under "Atomizer".

DIMENSIONS

45º Connection for Pilot

R

U

1/4" NPT Pressure Tap

E dia.

GG NPT Oil Inle t

1/4" NPT Pressure Tap

V-Hole on a W-Bolt Circle Z - # of Holes

AA

O Hole on a P Bolt Circle Q # of Holes

2.00

M

L

B 150 ANSI  Raised Flange Gas Inlet

A Main Air Con- nection (ANSI)

.50

1/4" NPT Air Tap

3° Taper

J

1/4" NPT Fuel Tap

K

CC NPT Pilot Connection

BB

I 

EE

1" NPT UV Connection

3/4" NPT Observation Por t

DD NPT Inlet (Steam or Compressed Air)

FF

C Hole on a D Bolt Circle F # of Holes

HH NPT Observation Port

.50 Mounting Flange

E

BB Min. Tile  Length (Refractory tile not by FNAC)

II Minimum Clearance for Atomizer Removal

see page 3 for dimension chart

DIMENSIONS SHOWN ARE SUBJECT TO CHANGE. PLEASE OBTAIN CERTIFIED PRINTS FROM FIVES NORTH AMERICAN COMBUSTION, INC. IF SPACE LIMITATIONS OR OTHER CONSIDERATIONS MAKE EXACT DIMENSION(S) CRITICAL .

Bulletin 6795 page 3

Made with FlippingBook flipbook maker