Dimensions 5514 Page 2
All 5514
5514- /LC, L4, L9 (jacketed tile) dimensions in inches
Burner
Sensitrol TM
Recommended
AA
DD
designation
BB
CC
wt - lb
oil valve
pilot tip
5514-6 5514-7
¾ ¾ ¾ ¾
83⁄8 93⁄8
287⁄16 30 ¼ 3613⁄16 4011⁄16 489⁄16 52 ¼
210 240 355 455 800
1813-02-C 1813-02-D 1813-02-D 1813-02-D
4021-12 4025-0-T 4025-0-T 4025-0-T 4025-2-T 4025-2-T
16 17
5514-8-A 5514-8-B 5514-9 5514-10
18 ¾
1215⁄16 1215⁄16 147⁄8 165⁄16
20
24 ¼ 27 ½
13⁄16 11⁄16
1813-01 1813-01
1000
A square threaded flange is used for sizes -6, -7, -8. SW style (suitable for slip-on or welded connection) inlet may be ordered as a special option. An SW inlet is stan- dard for -9 and -10 burners. Opening in furnace shell or outer wall must be ½ " larger than dimension "AA" to allow for mounting plate fillet and draft. Blank boss - This may be ordered as a special option with a 1 ½ " tap suitable for 5025-1-3T Oil Pilot, in which case North American will drill out ½ " web of refractory left in tile before shipment, and the burner nose will be positioned so none of its holes are in front of that opening. For -10 size, an appropriate 1 ½ " npt half-coupling will be added as a special option. 1" fpt for electrode or UV flame detector. Optional (recommended) Sensitrol TM Oil Valve and pipe nipple are not included as part of the burner assembly, and must be ordered separately. Dimensions Z and DD assume a 3⁄8 " close nipple between burner and Sensitrol Oil Valve (5514-6 through -8-B) and a ½ " close nipple between burner and Sensitrol Valve (5514-9 and -10). Applies when optional SW inlet is specified. Flanged connection--a standard North American square threaded flange is used. Optional 8773 flex tubing purchased separately from North American.
ANSI or SW flanges: Flat face companion flanges and full face gaskets are supplied with this equipment. Do not use raised face flanges that may damage mating flange.
ORDERING INFORMATION
5514 -
_ _ _
/ _ _
/ _ _ _ _
Burner Nose
Product Size Connection 6 ................. 3" 7.................. 4" 8-A ........... 6" 8-B ............ 6" 9 ................. 8" 10 ...............10"
Tile BO.... burner only LX..... refractory tile (no jacket) LC ..... steel tile jacket L4..... 304 stainless jacket L9..... 309 stainless jacket
Capacity
Material
1.0......main air capacity 1.1 .......1.1 x main air capacity 1.2 ......1.2 x main air capacity 1.3 ......1.3 x main air capacity
H ....cast iron
A ....alloy
Example 1 Example 2 Example 3
5514-8-A/LC/1.2A Fireall oil burner complete with carbon steel jacketed tile and 1.2 capacity alloy nose
5514-6/BO/1.0H Fireall oil burner only with standard capacity iron nose
5514-9/LX/1.2H Fireall oil burner complete with refractory tile and 1.2 capacity iron nose
Note: See Supplement 6514-6 for cross referencing old product numbers.
WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.
CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237
Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com
Made with FlippingBook flipbook maker