Specifications | 8880 Panels
SPECIFICATIONS and FEATURES
8"
— Rugged Fiberglass Enclosure size: 12" H × 10" W × 6" D
— NEMA 4X and 12 rated enclosure
— Power required: Maximum 5 amps at 120/1/60 VAC
Burner can be started remotely or locally (depending on wiring) Lockout Tag-out feature Safe Start Check Quick flip latches for easy access inside box
13 1 ⁄
8 "
— Clear plexiglass door to view status LEDs
— Stand alone unit or used with Main Panel (ordered separately)
— Compatible with flame rod, standard Honeywell UV detector (C7027 or C7035) and self-check Honeywell UV detector (C7061A)
— Used on pilot ignited systems, direct spark systems (with or without low-fire valve) or manually ignited systems
Mounting dimensions (provide drawing)
Standard drawings (Custom drawings available at additional cost) Flame Relay Reset Pushbutton on the front of the Flame relay
— Optional Flame Relay Reset on door
Local Burner On/Off Selector Switch Local Burner Start Pushbutton Visible indication on the Honeywell RM 7890 Flame Relay "POWER" LED on Flame Relay- Lit whenever flame relay is powered
"PILOT" LED on flame relay - Lit whenever terminal "8" (ie, PILOT terminal) of flame relay is powered "FLAME" LED on flame relay - Lit whenever the presence of flame is detected by the flame relay "MAIN" LED on flame relay - Lit whenever terminal "9" (ie, MAIN terminal) of flame relay is powered "ALARM" LED on flame relay - Lit whenever terminal "4" (ie, ALARM terminal) of flame relay is powered Display unit that gives burner status, diagnostic, and flame strength information
— Optional Keyboard Display unit available for flame relay diagnostics
— UL or Canadian UL approvable
— Can be modified for customization.
— Flame Failure alarm output (120 VAC, 1 amp pilot duty). — Contact available to indicate "burner on" status
Bulletin 8880 Page 4