Combustion Catalog | Fives North American

Capacity | 4020 Nozzle-Mix Pilot Tip

Air pressure, osi Combustion air capacity, cfh

Gas pressure osi at 100% XSF

Flame length inches at 100% XSF

Flame Length

(stoic.) at 1.0 osi

Designation 4020-0-LP 4020-2-LP 4020-3-LP 4020-4-LP 4020-5-LP 4020-6-LP

0.1

0.25 1.0

2.0 4.0 at 0.1 osi at 1.0 osi at 0.1 osi at1.0 osi

55

90

160 385

— — —

— — — — —

0.5 0.5 0.4 0.4 0.5

6.7 6.5 4.6 3.6 5.0 3.0 4.0

7

11

6" — —

120 150 200 310 600

180

12 14 14

17

200 450

22 26 33 50 58

350 765 1085 535 1235 1665

19" 24" 36" 42" 22" 24" 28"

23 24 32

890 1895 3195 4535

0.25 0.25

4020-7-LP

1600 2540 4650 6645 9355

Reduced exit port 4020-_-LP pilots with higher capacity/high velocity flames

4020-6-LP/4 4050-6-LP/5 4020-7-LP/6

485 530

710 1620 790 1725

— —

— —

0.25 0.25 0.25

2.3 2.4 2.8

24 24 30

38 40 54

1100 1805 3765 5390 8195

Maximum nominal excess air at 0.25 osi = 150% at 1.0 osi = 300%. Maximum nominal excess fuel at 0.25 osi = 180% at 1.0 osi = 200% Flame Lengths listed on this page are for open still air. Actual lengths when fired in a burner body will vary. The reduced port models of the 4020-6 and -7 pilots provide stronger, higher capacity flames than the standard version with the same exit size.

Flame length (stoic.)

Air pressure, osi Combustion air capacity, cfh

Gas pressure osi at 100% XSF

Flame length inches at 100% XSF

Designation 4020-0-HP* 4020-2-HP 4020-3-HP 4020-4-HP 4020-5-HP 4020-6-HP 4020-7-HP

1.0

4.0

8.0

16.0

at 1.0 osi at 16 osi at 1.0 osi at 16 osi

at 16 osi

45

92

115

150 650 915

0.6

6.3

8

10 26 30 33 35 54 76

6"

150 230 350 550 970

307 430

450 650

1.0 1.2 1.0

14.2 15.1 13.5

18 18 19

14" 18" 20"

740 1000 1500

1100

1600 2350

0.9

15

30 35 44

21"

2250 2975 4050 4600 6580 9165

1.0 1.7

9.5

33" 48"

2155

10.5

Reduced exit port 4020-_-HP pilots with higher capacity/high velocity flames

4020-6-HP/4 4020-6-HP/5

800 860 1950

1860 2765

3915

1.3 1.2 2.2

10.5

35 35 44

45 52 64

30" 34"

2000 2960 4145 4160 5890 8503

9.7

4020-7-HP/6 38" Maximum nominal excess air at 4.0 osi = 100% at 16 osi = 120%. Maximum nominal excess fuel at 4.0 osi = 130% at 16 osi = 100%. Flame Lengths listed on this page are for open still air. Actual lengths when fired in a burner body will vary. * With optional 4-20667-1 Valve/Orifice. The reduced port models of the 4030-6 and-7 pilots provide stronger, higher capacity flames than the standard version with the same exit size. 21.4

Gas pressure osi at 50% XSF

Air pressure, osi Combustion air capacity, cfh

Flame length inches at 50% XSF

Flame length (stoic.)

Designation 4020-3A-CB 4020-3-CB 4020-4-CB

1.0 150 225 360

4.0

8.0

16.0

at 1.0 osi at 16 osi at 1.0 osi at 16 osi

at 16 osi

290

410

610

1.2

16.3 23.5 14.0 14.5

15 16 18 24

16 18

12" 14" 15"

465 670

700 1030 950 1370

1.1 1.1

20 30

4020-5-CB 21" Maximum nominal excess air at 4.0 osi = 180% at 16 osi = 200% Maximum nominal excess fuel at 4.0 osi = 80% at 16 osi = 50%. 640 1300 1790 2520 1.2

Bulletin 4020 Page 3

Made with FlippingBook flipbook maker