Bulletin 8200 Page 5

Digital Inputs (Quantity 11) Voltage: 24 VDC Current: 4 mA nominal

Processor and I/O (Panel Mounted) Operating temperature: 0 to 130°F (–17 to 55°C) Approvals: CE, CSA, UL, CUL Power supply - Voltage: 85 to 264 VAC Power Supply - Current: 0.3 A at 120 VAC (0.15 A at 240 VAC) Line Frequency: 50/60 Hz Power Dissipation: 18.5 W Built in 24VDC Power Supply: 400mA Max (not for customer use) Dimensions: 9.75" x 4.57" x 3" (248 x 116 x 75 mm) Profinet Port Address: 10.1.220.198 O perator Interface Terminal (Door Mounted) Operating Temperature: 32 to 122°F (0 to 50°C) Enclosure Type 4X ( Indoor use only) Approvals: CE, CSA, UL, CUL Listed 74D7 Power Supply Voltage: 24 VDC (19.2 to 28.8 VDC) Power Supply Current: 0.44 A Dimensions - Front Panel: 8.424" x 6.22" (214 x 158 mm) Dimensions - Panel Cutout : 7.756" x 5.551" (197 x 141 mm) Display: 7" Touch screen with 8 pushbuttons Profinet Port Address: 10.1.220.199

Digital Outputs (Quantity 7) Type: Relay, Dry Contact Voltage: 5 to 30 VDC or 5 to 250 VAC Current: 2.0 A max Analog Inputs - Current (Quantity 8) Range: 0 to 20 m A Impedance: 250 ohm

Max Voltage: +/-35 VDC Max Current: +/-40 mA Cable Length: 100 meters twisted and shielded Analog Outputs (Quantity 4) Range: 0 to 20 mA Load Impedance: <600 ohms Cable Length: 100 meters twisted and shielded

C ontrol Valve Actuators Modulating Accuracy: Minimum 160 repositions through 90 degrees of travel are recommended (North American 1615 series or similar). Note: Low accuracy actuators will likely produce large flow variations and continuous hunting. Models with 55 repositions through 90 degrees of travel are not recommended.

Thermocouple Inputs (Quantity 3) Range: Available type selection and the corresponding ranges are listed below:

External 24 VDC Power Supply (Required) Power Supply - Voltage: 19.2 to 28.8 VDC Power Supply - Current: 0.64 Amp (minimum for 8200)

T/C Type

T/C Range (°F)

T/C Range (°C)

J

-100 - 1400 -100 - 2500 -100 - 2372

-73 - 760 -73 - 1371 -73 - 1300 -18 - 1768 -18 - 1768

K N R S

0 - 3214 0 - 3214

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.