Wiring and Dimensions | 8351 Furnace Pressure Controller

Bulletin 8351C-2013 Page 3

WIRING DIAGRAM

8351-C-2013 EPIC III SLOT A

4-20 CONTROL ACTUATOR

F

OUT 1 A

OUT

H

T1

4-20 A

8244 PRESSURE TRANSMITTER NOTE #3

IN

24VDC POWER SUPPLY REQUIRED

S1

included with model 8351-C-2013-PS

(Isolated Contacts)

SLOT B

TYP. 120VAC BIDIRECTIONAL MOTOR

H

L3 K3 J3

CLOSES TO INC PV

5A

120VAC

OUT3

N

CLOSE DAMPER

can also be used for 24VAC or shaded pole motors

OPEN DAMPER

L4 K4

CLOSES TO DEC PV

5A OUT4

NOTES:

1. 2 AMP MAX. LOAD 2. SPRING LOCK WIRE TERMINALS. PRESS ORANGE RELEASE TAB TO REMOVE WIRE. SOLID OR TINNED WIRE IS RECOMMENDED. 3. PRESSURE TRANSMITTER RANGE MUST AGREE WITH r9.LO & r9.HI PARAMETER SETTERS IN 8351-C-2013.

REAR VIEW

SLOT C

A

B

(VACANT)

98 99 CF CD CE C

F1 G1 H1

L3 K3 J3 L4 K4

H N

98 99

100-240VAC

T1 S1 R1

DIMENSIONS SHOWN ARE SUBJECT TO CHANGE. PLEASE OBTAIN CERTIFIED PRINTS FROM FIVES NORTH AMERICAN COMBUSTION, INC. IF SPACE LIMITATIONS OR OTHER CONSIDERATIONS MAKE EXACT DIMENSION(S) CRITICAL .

WARNING: Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.

CONTACT fna.sales@fivesgroup.com T +1 800 626 3477 - F +1 216 373 4237

Fives North American Combustion, Inc. 4455 East 71st Street - Cleveland, OH 44105 - USA www.fivesgroup.com