Rapid Build Masonry Joist Hanger RB–JHI

— Suitable for use with Open Web Joists, I–Joists and trusses — Non return hangers are suitable with no masonry above. Return only required for increased load capacity

In Situ

— No masonry is required above the hanger (unless stated for increased load capacity). — The masonry supporting the hanger must be cured for 3 days prior to loading the floor. — The RB–JHI/RB–JHIR does not provide restraint, therefore restraint straps may be required (see pages 81 – 82)

Load Data

Characteristic Capacity (kN)

Fixings (3.4 x 35mm)

Masonry Above (Min 675mm)

Hanger Type

Masonry Crushing Strength

Uplift

3.5N/mm 2

7.0N/mm 2

2.8N/mm 2

Incoming

RB–JHI

No

2

n/a

12.56

15.71

21.26

2

2.00 4.50

RB–JHI

Yes

19.83

24.79

39.60

5 (2)

Enhanced Uplift (2)

Hanger Depth (mm)

Min Timber Depth (mm)

— Fixings into the incoming joist/truss are required to resist uplift — Increased uplift figures can be achieved by nailing the additional triangular nail holes into incoming member — Web stiffeners required for I–Joists, 2No end blocks required for Open Web Joists & minimum bottom chord depth/vertical required for trusses — Requires minimum full storey of masonry above to achieve values

150

84

175 – 195 225 – 240

122 172 195 235 300 350

250 300 350 400

Incorrect Installation

MAX 6MM

NO GAP

MIN 250MM

MAX 3MM THICKNESS OF RB-TOP PLATE

Do not cut/modify the top flanges. These are critical to the performance.

Do not install the hanger with a gap exceeding 6mm between the joist/truss and the hanger.

Do not install the hanger with a gap between the hanger and the face of the block work.

Do not install the hanger onto a timber wall plate.