Restraint Straps (Domestic Floors)

Lateral restraint of the walls can be provided by the floor, the restraint must be provided parallel and perpendicular to the floor joists.

ROOF

The type of restraint straps required and the centres at which they are placed depend on the joist end detail and region in which the house is built.

3RD STOREY

The information we provide has been compiled using the minimum requirement from Building Regulations 2010 approved document A, Scottish Building regulation domestic, NHBC standards and British Standard BS 5628–1;2005 Annex D.

2ND FLOOR

2ND STOREY

These have been issued as guidance only, the overall responsibility lies with the Building Designer.

1ST FLOOR

1ST STOREY

For 3rd floor and above please refer to the building standards or building designer for guidance.

GROUND FLOOR

3 STOREY HOUSE

All straps require a full storey of block work above to achieve the full 8kN declared load capacity.

Parallel Restraint

PSB strap with built in detail

— The strap should be nailed with a minimum of 8No 3.4x35mm Square Twist Nails into the joist top flange/chord

Floor Level

Detail

Region

Ground Floor

1st Floor

2nd Floor

Where joists have a minimum bearing of 90mm no additional restraint is required (additional PSB straps required each side of opening where openings exceed 600mm)

PSB straps required at 2m max centres

England & Wales

Built in

Scotland

Please refer to page 139 for further information on PSB straps

PST strap with non–restraint hanger

— The strap should be nailed with a minimum of 8No 3.4x35mm Square Twist Nails into the joist top flange/chord

Floor Level

Detail

Region

Ground Floor

1st Floor

2nd Floor

Non–Restraint Hangers (JHI/JHIR/ RB–JHI/RB–JHIR)

England & Wales

PST or PSC required at 2m max centres

PST or PSC required at 2m max centres

PST or PSC required at 1.25m max centres

Scotland

Please refer to page 139 for further information on PST/PSC straps

PSB strap with restraint hanger

— The strap should be nailed with a minimum of 8No 3.4x35mm Square Twist Nails into the joist bottom flange/chord

Floor Level

Detail

Region

Ground Floor

1st Floor

2nd Floor

PSB required at 2m max centres PSB required at 1.25m max centres

Restraint Hang- ers (RA/HRAD/ RADS)

No additional restraint is required (additional PSB straps required each side of opening where openings exceed 600mm)

England & Wales

Scotland

Please refer to page 139 for further information on PSB straps